Appendix
B-5
7SA6 Manual
C53000-G1176-C133-1
1103 FullScaleVolt. Power System Data
2
1.0..1200.0 kV 400.0 kV Measurement: Full Scale Voltage
(100%)
1104 FullScaleCurr. Power System Data
2
10..5000 A 1000 A Measurement: Full Scale Current
(100%)
1105 Line Angle Power System Data
2
30..89 ° 85 ° Line Angle
1110 x’ Power System Data
2
0.005..6.500 Ohm / km 0.150 Ohm / km x’ - Line Reactance per length unit
1111 Line Length Power System Data
2
1.0..1000.0 km 100.0 km Line Length
1112 x’ Power System Data
2
0.005..10.000 Ohm / mile 0.242 Ohm / mile x’ - Line Reactance per length unit
1113 Line Length Power System Data
2
0.6..650.0 Miles 62.1 Miles Line Length
1116 RE/RL(Z1) Power System Data
2
-.33..7.00 1.00 Zero seq. comp. factor RE/RL for Z1
1117 XE/XL(Z1) Power System Data
2
-.33..7.00 1.00 Zero seq. comp. factor XE/XL for Z1
1118 RE/RL(Z1B...Z5) Power System Data
2
-.33..7.00 1.00 Zero seq. comp.factor RE/RL for
Z1B...Z5
1119 XE/XL(Z1B...Z5) Power System Data
2
-.33..7.00 1.00 Zero seq. comp.factor XE/XL for
Z1B...Z5
1120 K0 (Z1) Power System Data
2
0.000..4.000 1.000 Zero seq. comp. factor K0 for zone Z1
1121 Angle K0(Z1) Power System Data
2
-135.00..135.00 ° 0.00 ° Zero seq. comp. angle for zone Z1
1122 K0 (> Z1) Power System Data
2
0.000..4.000 1.000 Zero seq.comp.factor K0,higher zones
>Z1
1123 AngleI K0(> Z1) Power System Data
2
-135.00..135.00 ° 0.00 ° Zero seq. comp. angle, higher zones
>Z1
1126 RM/RL ParalLine Power System Data
2
0.00..8.00 0.00 Mutual Parallel Line comp. ratio RM/
RL
1127 XM/XL ParalLine Power System Data
2
0.00..8.00 0.00 Mutual Parallel Line comp. ratio XM/XL
1128 RATIO Par. Comp Power System Data
2
50..95 % 85 % Neutral current RATIO Parallel Line
Comp
1130A PoleOpenCurrent Power System Data
2
0.05..1.00 A 0.10 A Pole Open Current Threshold
1131A PoleOpenVoltage Power System Data
2
2..70 V 30 V Pole Open Voltage Threshold
1132A SI Time all Cl. Power System Data
2
0.01..30.00 sec 0.05 sec Seal-in Time after ALL closures
1134 Line Closure Power System Data
2
Manual Close BI only
Current OR Voltage or Man-
ual close BI
CBaux OR Current or Man-
ual close BI
Current flow or Manual close
BI
Manual Close BI only Recognition of Line Closures with
1135 Reset Trip CMD Power System Data
2
with Pole Open Current
Threshold only
with CBaux AND Pole Open
Current
with Pole Open Current
Threshold only
RESET of Trip Command
1140A I-CTsat. Thres. Power System Data
2
0.2..50.0 A; ∞ 10.0 A CT Saturation Threshold
1150A SI Time Man.Cl Power System Data
2
0.01..30.00 sec 0.30 sec Seal-in Time after MANUAL closures
Addr. Setting Title Function Setting Options Default Setting Comments