Appendix
B-4
212 Usync connect. Power System Data
1
L1-E
L2-E
L3-E
L1-L2
L2-L3
L3-L1
L1-L2 VT connection for sync. voltage
214 A ϕ Usync-Uline Power System Data
1
0..360 ° 0 ° Angle adjustment Usync-Uline
215 U-line / Usync Power System Data
1
0.80..1.20 1.00 Matching ratio U-line / Usync
220 I4 transformer Power System Data
1
not connected
Neutral Current (of the pro-
tected line)
Neutral Current of the paral-
lel line
Starpoint Curr. of earthed
power transf.
Neutral Current (of the pro-
tected line)
I4 current transformer is
221 I4/Iph CT Power System Data
1
0.010..5.000 1.000 Matching ratio I4/Iph for CT’s
230 Rated Frequency Power System Data
1
50 Hz
60 Hz
50 Hz Rated Frequency
235 PHASE SEQ. Power System Data
1
L1 L2 L3
L1 L3 L2
L1 L2 L3 Phase Sequence
236 Distance Unit Power System Data
1
km
Miles
km Distance measurement unit
237 Format Z0/Z1 Power System Data
1
Zero seq. comp. factors RE/
RL and XE/XL
Zero seq. comp. factor K0
and angle(K0)
Zero seq. comp. factors RE/
RL and XE/XL
Setting format for zero seq.comp. for-
mat
239 T-CB close Power System Data
1
0.01..0.60 sec 0.06 sec Closing (operating) time of CB
240 TMin TRIP CMD Power System Data
1
0.02..30.00 sec 0.10 sec Minimum TRIP Command Duration
241 TMax CLOSE CMD Power System Data
1
0.01..30.00 sec 0.10 sec Maximum Close Command Duration
242 T-CBtest-dead Power System Data
1
0.00..30.00 sec 0.10 sec Dead Time for CB test-auto
reclosure
302 CHANGE Change Group Group A
Group B
Group C
Group D
Binary Input
Protocol
Group A Change to Another Setting Group
402A WAVEFORMTRIG-
GER
Oscillographic Fault
Records
Save with Pickup
Save with TRIP
Start with TRIP
Save with Pickup Waveform Capture
403A WAVEFORM DATA Oscillographic Fault
Records
Fault event
Power System fault
Fault event Scope of Waveform Data
410 MAX. LENGTH Oscillographic Fault
Records
0.30..5.00 sec 1.00 sec Waveform Capture
411 PRE. TRIG. TIME Oscillographic Fault
Records
0.05..0.50 sec 0.10 sec Captured Waveform Prior to Trigger
412 POST REC. TIME Oscillographic Fault
Records
0.05..0.50 sec 0.10 sec Captured Waveform after Event
415 BinIn CAPT.TIME Oscillographic Fault
Records
0.10..5.00 sec; 0.50 sec Capture Time via Binary Input
610 FltDisp.LED/LCD Device Display Targets on every
Pickup
Display Targets on TRIP
only
Display Targets on every
Pickup
Fault Display on LED / LCD
615 Spont. FltDisp. Device NO
YES
NO Spontaneous display of flt.annuncia-
tions
Addr. Setting Title Function Setting Options Default Setting Comments

Table of Contents

Other manuals for Siemens siprotec 7SA6

Related product manuals