Appendix
B-3
7SA6 Manual
C53000-G1176-C133-1
138 Fault Locator Scope of Functions Disabled
Enabled
with BCD-output
Enabled Fault Locator
139 BREAKER FAIL-
URE
Scope of Functions Disabled
Enabled
Disabled Breaker Failure Protection
140 TripCirc.Superv Scope of Functions Disabled
1 trip circuit
2 trip circuits
3 trip circuits
Disabled Trip Circuit Supervision
142 Ther. OVERLOAD Scope of Functions Disabled
Enabled
Disabled Thermal overload protection
150 AnalogOutput B1 Scope of Functions Disabled
IL2 [%]
UL23 [%]
|P| [%]
|Q| [%]
Fault location d [%]
Fault location d [km]
Trip current Imax [primary]
Disabled Analog Output B1 (Port B)
151 AnalogOutput B2 Scope of Functions Disabled
IL2 [%]
UL23 [%]
|P| [%]
|Q| [%]
Fault location d [%]
Fault location d [km]
Trip current Imax [primary]
Disabled Analog Output B2 (Port B)
152 AnalogOutput D1 Scope of Functions Disabled
IL2 [%]
UL23 [%]
|P| [%]
|Q| [%]
Fault location d [%]
Fault location d [km]
Trip current Imax [primary]
Disabled Analog Output D1 (Port D)
153 AnalogOutput D2 Scope of Functions Disabled
IL2 [%]
UL23 [%]
|P| [%]
|Q| [%]
Fault location d [%]
Fault location d [km]
Trip current Imax [primary]
Disabled Analog Output D2 (Port D)
201 CT Starpoint Power System Data
1
towards Line
towards Busbar
towards Line CT Starpoint
203 Unom PRIMARY Power System Data
1
1.0..1200.0 kV 400.0 kV Rated Primary Voltage
204 Unom SECOND-
ARY
Power System Data
1
80..125 V 100 V Rated Secondary Voltage (L-L)
205 CT PRIMARY Power System Data
1
10..5000 A 1000 A CT Rated Primary Current
206 CT SECONDARY Power System Data
1
1A
5A
1A CT Rated Secondary Current
207 SystemStarpoint Power System Data
1
Solid Earthed
Peterson-Coil earthed
Isolated
Solid Earthed
System Starpoint is
210 U4 transformer Power System Data
1
not connected
Udelta transformer
Usync transformer
Ux reference transformer
not connected U4 voltage transformer is
211 Uph / Udelta Power System Data
1
0.10..9.99 1.73 Matching ratio Phase-VT To Open-
Delta-VT
Addr. Setting Title Function Setting Options Default Setting Comments