Appendix
B-18
3516 Usync> U-line< Synchronism and
Voltage Check
YES
NO
NO Live bus / dead line check before AR
3517 Usync< U-line> Synchronism and
Voltage Check
YES
NO
NO Dead bus / live line check before AR
3518 Usync< U-line< Synchronism and
Voltage Check
YES
NO
NO Dead bus / dead line check before AR
3519 OVERRIDE Synchronism and
Voltage Check
YES
NO
NO Override of any check before AR
3530 Op.mode with MC Synchronism and
Voltage Check
with consideration of CB
closing time
without consideration of CB
closing time
without consideration of CB
closing time
Operating mode with Man.Cl
3531 MC maxVolt.Diff Synchronism and
Voltage Check
1.0..40.0 V 2.0 V Maximum voltage difference
3532 MC maxFreq.Diff Synchronism and
Voltage Check
0.03..2.00 Hz 0.10 Hz Maximum frequency difference
3533 MC maxAngleDiff Synchronism and
Voltage Check
2..60 ° 10 ° Maximum angle difference
3535A MC SYNCHR Synchronism and
Voltage Check
YES
NO
YES Live bus / live line and Sync before MC
3536 MC Usyn> Uline< Synchronism and
Voltage Check
YES
NO
NO Live bus / dead line check before
Man.Cl
3537 MC Usyn< Uline> Synchronism and
Voltage Check
YES
NO
NO Dead bus / live line check before
Man.Cl
3538 MC Usyn< Uline< Synchronism and
Voltage Check
YES
NO
NO Dead bus / dead line check before
Man.Cl
3539 MC O/RIDE Synchronism and
Voltage Check
YES
NO
NO Override of any check before Man.Cl
3701 Uph-e>(>) Voltage Protection OFF
Alarm Only
ON
OFF Operating mode Uph-e overvoltage
prot.
3702 Uph-e> Voltage Protection 1.0..170.0 V 85.0 V Uph-e> Pickup
3703 T Uph-e> Voltage Protection 0.00..30.00 sec; 2.00 sec T Uph-e> Time Delay
3704 Uph-e>> Voltage Protection 1.0..170.0 V 100.0 V Uph-e>> Pickup
3705 T Uph-e>> Voltage Protection 0.00..30.00 sec; 1.00 sec T Uph-e>> Time Delay
3709A Uph-e>(>) RESET Voltage Protection 0.50..0.98 0.98 Uph-e>(>) Reset ratio
3711 Uph-ph>(>) Voltage Protection OFF
Alarm Only
ON
OFF Operating mode Uph-ph overvoltage
prot.
3712 Uph-ph> Voltage Protection 2.0..220.0 V 150.0 V Uph-ph> Pickup
3713 T Uph-ph> Voltage Protection 0.00..30.00 sec; 2.00 sec T Uph-ph> Time Delay
3714 Uph-ph>> Voltage Protection 2.0..220.0 V 175.0 V Uph-ph>> Pickup
3715 T Uph-ph>> Voltage Protection 0.00..30.00 sec; 1.00 sec T Uph-ph>> Time Delay
3719A Uphph>(>) RESET Voltage Protection 0.50..0.98 0.98 Uph-ph>(>) Reset ratio
3721 3U0>(>) (or Ux) Voltage Protection OFF
Alarm Only
ON
OFF Operating mode 3U0 (or Ux) overvolt-
age
3722 3U0> Voltage Protection 1.0..220.0 V 30.0 V 3U0> Pickup (or Ux>)
3723 T 3U0> Voltage Protection 0.00..30.00 sec; 2.00 sec T 3U0> Time Delay (or T Ux>)
3724 3U0>> Voltage Protection 1.0..220.0 V 50.0 V 3U0>> Pickup (or Ux>>)
3725 T 3U0>> Voltage Protection 0.00..30.00 sec; 1.00 sec T 3U0>> Time Delay (or T Ux>>)
3729A 3U0>(>) RESET Voltage Protection 0.50..0.98 0.95 3U0>(>) Reset ratio (or Ux)
Addr. Setting Title Function Setting Options Default Setting Comments