Appendix
B-19
7SA6 Manual
C53000-G1176-C133-1
3731 U1>(>) Voltage Protection OFF
Alarm Only
ON
OFF Operating mode U1 overvoltage prot.
3732 U1> Voltage Protection 2.0..220.0 V 150.0 V U1> Pickup
3733 T U1> Voltage Protection 0.00..30.00 sec; ∞ 2.00 sec T U1> Time Delay
3734 U1>> Voltage Protection 2.0..220.0 V 175.0 V U1>> Pickup
3735 T U1>> Voltage Protection 0.00..30.00 sec; ∞ 1.00 sec T U1>> Time Delay
3739A U1>(>) RESET Voltage Protection 0.50..0.98 0.98 U1>(>) Reset ratio
3741 U2>(>) Voltage Protection OFF
Alarm Only
ON
OFF Operating mode U2 overvoltage prot.
3742 U2> Voltage Protection 2.0..220.0 V 30.0 V U2> Pickup
3743 T U2> Voltage Protection 0.00..30.00 sec; ∞ 2.00 sec T U2> Time Delay
3744 U2>> Voltage Protection 2.0..220.0 V 50.0 V U2>> Pickup
3745 T U2>> Voltage Protection 0.00..30.00 sec; ∞ 1.00 sec T U2>> Time Delay
3749A U2>(>) RESET Voltage Protection 0.50..0.98 0.98 U2>(>) Reset ratio
3751 Uph-e<(<) Voltage Protection OFF
Alarm Only
ON
OFF Operating mode Uph-e undervoltage
prot.
3752 Uph-e< Voltage Protection 1.0..100.0 V 30.0 V Uph-e< Pickup
3753 T Uph-e< Voltage Protection 0.00..30.00 sec; ∞ 2.00 sec T Uph-e< Time Delay
3754 Uph-e<< Voltage Protection 1.0..100.0 V 10.0 V Uph-e<< Pickup
3755 T Uph-e<< Voltage Protection 0.00..30.00 sec; ∞ 1.00 sec T Uph-e<< Time Delay
3758 CURR.SUP. Uphe< Voltage Protection ON
OFF
ON Current supervision (Uph-e)
3761 Uph-ph<(<) Voltage Protection OFF
Alarm Only
ON
OFF Operating mode Uph-ph undervoltage
prot.
3762 Uph-ph< Voltage Protection 1.0..175.0 V 50.0 V Uph-ph< Pickup
3763 T Uph-ph< Voltage Protection 0.00..30.00 sec; ∞ 2.00 sec T Uph-ph< Time Delay
3764 Uph-ph<< Voltage Protection 1.0..175.0 V 17.0 V Uph-ph<< Pickup
3765 T Uphph<< Voltage Protection 0.00..30.00 sec; ∞ 1.00 sec T Uph-ph<< Time Delay
3768 CURR.SUP.Uphph
<
Voltage Protection ON
OFF
ON Current supervision (Uph-ph)
3771 U1<(<) Voltage Protection OFF
Alarm Only
ON
OFF Operating mode U1 undervoltage prot.
3772 U1< Voltage Protection 1.0..100.0 V 30.0 V U1< Pickup
3773 T U1< Voltage Protection 0.00..30.00 sec; ∞ 2.00 sec T U1< Time Delay
3774 U1<< Voltage Protection 1.0..100.0 V 10.0 V U1<< Pickup
3775 T U1<< Voltage Protection 0.00..30.00 sec; ∞ 1.00 sec T U1<< Time Delay
3778 CURR.SUP.U1< Voltage Protection ON
OFF
ON Current supervision (U1)
3802 START Fault Locator Pickup
TRIP
Pickup Start fault locator with
3805 Paral.Line Comp Fault Locator NO
YES
NO Mutual coupling parall.line compensa-
tion
3806 Load Compensat. Fault Locator NO
YES
NO Load Compensation
3811 Tmax OUTPUT
BCD
Fault Locator 0.10..30.00 sec 0.30 sec Maximum output time via BCD
Addr. Setting Title Function Setting Options Default Setting Comments