Appendix
B-24
193 Alarm: NO calibration data available
(Alarm NO calibr)
Device OUT ON
OFF
* LED BO 135 181 1 GI
194 Error: Neutral CT different from
MLFB (Error neutralCT)
Device OUT ON
OFF
* LED BO 135 180 1 GI
195 Failure: Broken Conductor (Fail Con-
ductor)
Measurement
Supervision
OUT ON
OFF
* LED BO 135 195 1 GI
196 Fuse Fail Monitor is switched OFF
(Fuse Fail M.OFF)
Measurement
Supervision
OUT ON
OFF
* LED BO 135 196 1 GI
197 Measurement Supervision is
switched OFF (MeasSup OFF)
Measurement
Supervision
OUT ON
OFF
* LED BO 135 197 1 GI
203 Waveform data deleted (Wave.
deleted)
Oscillographic
Fault Records
OUT_Ev ON * LED BO 135 203 1
273 Set Point Phase L1 dmd> (SP. IL1
dmd>)
Set Points (Mea-
sured Values)
OUT on
off
* LED BO 135 230 1 GI
274 Set Point Phase L2 dmd> (SP. IL2
dmd>)
Set Points (Mea-
sured Values)
OUT on
off
* LED BO 135 234 1 GI
275 Set Point Phase L3 dmd> (SP. IL3
dmd>)
Set Points (Mea-
sured Values)
OUT on
off
* LED BO 135 235 1 GI
276 Set Point positive sequence I1dmd>
(SP. I1dmd>)
Set Points (Mea-
sured Values)
OUT on
off
* LED BO 135 236 1 GI
277 Set Point |Pdmd|> (SP. |Pdmd|>) Set Points (Mea-
sured Values)
OUT on
off
* LED BO 135 237 1 GI
278 Set Point |Qdmd|> (SP. |Qdmd|>) Set Points (Mea-
sured Values)
OUT on
off
* LED BO 135 238 1 GI
279 Set Point |Sdmd|> (SP. |Sdmd|>) Set Points (Mea-
sured Values)
OUT on
off
* LED BO 135 239 1 GI
285 Power factor alarm (cosϕ alarm) Set Points (Mea-
sured Values)
OUT on
off
* LED BO 135 245 1 GI
351 >Circuit breaker aux. contact: Pole
L1 (>CB Aux. L1)
Power System
Data 2
SP * * LED BI BO 150 1 1 GI
352 >Circuit breaker aux. contact: Pole
L2 (>CB Aux. L2)
Power System
Data 2
SP * * LED BI BO 150 2 1 GI
353 >Circuit breaker aux. contact: Pole
L3 (>CB Aux. L3)
Power System
Data 2
SP * * LED BI BO 150 3 1 GI
356 >Manual close signal (>Manual
Close)
Power System
Data 2
SP * * LED BI BO 150 6 1 GI
357 >Block all Close commands from
external (>Close Cmd. Blk)
Power System
Data 2
SP ON
OFF
* LED BI BO 150 7 1 GI
361 >Failure: Feeder VT (MCB tripped)
(>FAIL:Feeder VT)
Power System
Data 2
SP ON
OFF
* LED BI BO 128 38 1 GI
362 >Failure: Busbar VT (MCB tripped)
(>FAIL:Bus VT)
Power System
Data 2
SP ON
OFF
* LED BI BO 150 12 1 GI
366 >CB1 Pole L1 (for AR,CB-Test)
(>CB1 Pole L1)
Power System
Data 2
SP * * LED BI BO 150 66 1 GI
367 >CB1 Pole L2 (for AR,CB-Test)
(>CB1 Pole L2)
Power System
Data 2
SP * * LED BI BO 150 67 1 GI
368 >CB1 Pole L3 (for AR,CB-Test)
(>CB1 Pole L3)
Power System
Data 2
SP * * LED BI BO 150 68 1 GI
F.No. Description Function Type of
Information
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information-No
Data Unit (ASDU)
General Interrogation