Appendix
B-36
1511 Thermal Overload Protection OFF
(Th.Overload OFF)
Thermal Overload OUT ON
OFF
* LED BO 167 11 1 GI
1512 Thermal Overload Protection
BLOKKED (Th.Overload BLK)
Thermal Overload OUT ON
OFF
ON
OFF
LED BO 167 12 1 GI
1513 Thermal Overload Protection
ACTIVE (Th.O/L ACTIVE)
Thermal Overload OUT ON
OFF
* LED BO 167 13 1 GI
1515 Th. Overload: Current Alarm (I
alarm) (Th.O/L I Alarm)
Thermal Overload OUT ON
OFF
* LED BO 167 15 1 GI
1516 Th. Overload Alarm: Near Thermal
Trip (Th.O/L Θ Alarm)
Thermal Overload OUT ON
OFF
* LED BO 167 16 1 GI
1517 Th. Overload Pickup before trip
(Th.O/L Pickup)
Thermal Overload OUT ON
OFF
* LED BO 167 17 1 GI
1521 Th. Overload TRIP command (Th.O/
L TRIP)
Thermal Overload OUT * ON M LED BO 167 21 1
2054 Emergency mode (Emer. mode) Backup overcur-
rent
OUT ON
OFF
ON
OFF
LED BO 128 37 1 GI
2701 >AR: Switch on auto-reclose func-
tion (>AR on)
Automatic Reclo-
sure
SP * * LED BI BO 40 1 1
2702 >AR: Switch off auto-reclose func-
tion (>AR off)
Automatic Reclo-
sure
SP * * LED BI BO 40 2 1
2703 >AR: Block auto-reclose function
(>AR block)
Automatic Reclo-
sure
SP ON
OFF
* LED BI BO 40 3 1 GI
2711 >External start of internal Auto
reclose (>AR Start)
Automatic Reclo-
sure
SP * ON LED BI BO 40 11 2 GI
2712 >AR: External trip L1 for AR start
(>Trip L1 AR)
Automatic Reclo-
sure
SP * ON LED BI BO 40 12 2 GI
2713 >AR: External trip L2 for AR start
(>Trip L2 AR)
Automatic Reclo-
sure
SP * ON LED BI BO 40 13 2 GI
2714 >AR: External trip L3 for AR start
(>Trip L3 AR)
Automatic Reclo-
sure
SP * ON LED BI BO 40 14 2 GI
2715 >AR: External 1pole trip for AR start
(>Trip 1pole AR)
Automatic Reclo-
sure
SP * ON LED BI BO 40 15 2 GI
2716 >AR: External 3pole trip for AR start
(>Trip 3pole AR)
Automatic Reclo-
sure
SP * ON LED BI BO 40 16 2 GI
2727 >AR: Remote Close signal (>AR
RemoteClose)
Automatic Reclo-
sure
SP * ON LED BI BO 40 22 2 GI
2731 >AR: Sync. release from ext. sync.-
check (>Sync.release)
Automatic Reclo-
sure
SP * * LED BI BO 40 31 2 GI
2737 >AR: Block 1pole AR-cycle
(>BLOCK 1pole AR)
Automatic Reclo-
sure
SP ON
OFF
* LED BI BO 40 32 1 GI
2738 >AR: Block 3pole AR-cycle
(>BLOCK 3pole AR)
Automatic Reclo-
sure
SP ON
OFF
* LED BI BO 40 33 1 GI
2739 >AR: Block 1phase-fault AR-cycle
(>BLK 1phase AR)
Automatic Reclo-
sure
SP ON
OFF
* LED BI BO 40 34 1 GI
2740 >AR: Block 2phase-fault AR-cycle
(>BLK 2phase AR)
Automatic Reclo-
sure
SP ON
OFF
* LED BI BO 40 35 1 GI
2741 >AR: Block 3phase-fault AR-cycle
(>BLK 3phase AR)
Automatic Reclo-
sure
SP ON
OFF
* LED BI BO 40 36 1 GI
F.No. Description Function Type of
Information
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information-No
Data Unit (ASDU)
General Interrogation