Appendix
B-37
7SA6 Manual
C53000-G1176-C133-1
2742 >AR: Block 1st AR-cycle (>BLK
1.AR-cycle)
Automatic Reclo-
sure
SP ON
OFF
* LED BI BO 40 37 1 GI
2743 >AR: Block 2nd AR-cycle (>BLK
2.AR-cycle)
Automatic Reclo-
sure
SP ON
OFF
* LED BI BO 40 38 1 GI
2744 >AR: Block 3rd AR-cycle (>BLK
3.AR-cycle)
Automatic Reclo-
sure
SP ON
OFF
* LED BI BO 40 39 1 GI
2745 >AR: Block 4th and higher AR-
cycles (>BLK 4.-n. AR)
Automatic Reclo-
sure
SP ON
OFF
* LED BI BO 40 40 1 GI
2746 >AR: External Trip for AR start
(>Trip for AR)
Automatic Reclo-
sure
SP * ON LED BI BO 40 41 2 GI
2747 >AR: External pickup L1 for AR start
(>Pickup L1 AR)
Automatic Reclo-
sure
SP * ON LED BI BO 40 42 2 GI
2748 >AR: External pickup L2 for AR start
(>Pickup L2 AR)
Automatic Reclo-
sure
SP * ON LED BI BO 40 43 2 GI
2749 >AR: External pickup L3 for AR start
(>Pickup L3 AR)
Automatic Reclo-
sure
SP * ON LED BI BO 40 44 2 GI
2750 >AR: External pickup 1phase for AR
start (>Pickup 1ph AR)
Automatic Reclo-
sure
SP * ON LED BI BO 40 45 2 GI
2751 >AR: External pickup 2phase for AR
start (>Pickup 2ph AR)
Automatic Reclo-
sure
SP * ON LED BI BO 40 46 2 GI
2752 >AR: External pickup 3phase for AR
start (>Pickup 3ph AR)
Automatic Reclo-
sure
SP * ON LED BI BO 40 47 2 GI
2781 AR: Auto-reclose is switched off (AR
off)
Automatic Reclo-
sure
OUT ON
OFF
* LED BO 40 81 1 GI
2782 AR: Auto-reclose is switched on (AR
on)
Automatic Reclo-
sure
IntSP * * LED BO 128 16 1 GI
2783 AR: Auto-reclose is blocked (AR is
blocked)
Automatic Reclo-
sure
OUT ON
OFF
* LED BO 40 83 1 GI
2784 AR: Auto-reclose is not ready (AR
not ready)
Automatic Reclo-
sure
OUT * ON LED BO 128 130 1 GI
2787 AR: Circuit breaker not ready (CB
not ready)
Automatic Reclo-
sure
OUT * * LED BO 40 87 1
2788 AR: CB ready monitoring window
expired (AR T-CBreadyExp)
Automatic Reclo-
sure
OUT * ON LED BO 40 88 2
2796 AR: Auto-reclose ON/OFF via BI
(AR on/off BI)
Automatic Reclo-
sure
IntSP * * LED BO
2801 AR in progress (AR in progress) Automatic Reclo-
sure
OUT * ON LED BO 40 101 2 GI
2809 AR: Start-signal monitoring time
expired (AR T-Start Exp)
Automatic Reclo-
sure
OUT * ON LED BO 40 174 1
2810 AR: Maximum dead time expired
(AR TdeadMax Exp)
Automatic Reclo-
sure
OUT * ON LED BO 40 175 1
2818 AR: Evolving fault recognition (AR
evolving Flt)
Automatic Reclo-
sure
OUT * ON LED BO 40 118 2 GI
2820 AR is set to operate after 1p trip only
(AR Program1pole)
Automatic Reclo-
sure
OUT * * LED BO 40 143 1
2821 AR dead time after evolving fault
(AR Td. evol.Flt)
Automatic Reclo-
sure
OUT * ON LED BO 40 197 2
F.No. Description Function Type of
Information
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information-No
Data Unit (ASDU)
General Interrogation