Appendix
B-45
7SA6 Manual
C53000-G1176-C133-1
3782 DistanceTime Out Reverse/Non-dir.
PICKUP (Dis.TimeOut Trv)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 161 2
3801 Distance protection: General trip
(Dis.Gen. Trip)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 201 2
3802 Distance TRIP command - Only
Phase L1 (Dis.Trip 1pL1)
Distance protec-
tion, general set-
tings
OUT * ON LED BO 28 202 2
3803 Distance TRIP command - Only
Phase L2 (Dis.Trip 1pL2)
Distance protec-
tion, general set-
tings
OUT * ON LED BO 28 203 2
3804 Distance TRIP command - Only
Phase L3 (Dis.Trip 1pL3)
Distance protec-
tion, general set-
tings
OUT * ON LED BO 28 204 2
3805 Distance TRIP command Phases
L123 (Dis.Trip 3p)
Distance protec-
tion, general set-
tings
OUT * ON LED BO 28 205 2
3811 Distance TRIP single-phase Z1
(Dis.TripZ1/1p)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 211 2
3813 Distance TRIP single-phase Z1B
(Dis.TripZ1B1p)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 213 2
3816 Distance TRIP single-phase Z2
(Dis.TripZ2/1p)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 216 2
3817 Distance TRIP 3phase in Z2
(Dis.TripZ2/3p)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 217 2
3818 Distance TRIP 3phase in Z3
(Dis.TripZ3/T3)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 218 2
3819 Dist.: Trip by fault detection, forward
(Dis.Trip FD->)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 219 2
3820 Dist.: Trip by fault detec, rev/non-dir.
(Dis.Trip <->)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 220 2
3821 Distance TRIP 3phase in Z4
(Dis.TRIP 3p. Z4)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 209 2
3822 Distance TRIP 3phase in Z5
(Dis.TRIP 3p. Z5)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 210 2
3823 DisTRIP 3phase in Z1 with single-ph
Flt. (DisTRIP3p. Z1sf)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 224 2
3824 DisTRIP 3phase in Z1 with multi-ph
Flt. (DisTRIP3p. Z1mf)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 225 2
F.No. Description Function Type of
Information
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information-No
Data Unit (ASDU)
General Interrogation