Appendix
B-46
3825 DisTRIP 3phase in Z1B with single-
ph Flt (DisTRIP3p.Z1Bsf)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 244 2
3826 DisTRIP 3phase in Z1B with multi-ph
Flt. (DisTRIP3p Z1Bmf)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 245 2
3850 DisTRIP Z1B with Teleprotection
scheme (DisTRIP Z1B Tel)
Distance protec-
tion, general set-
tings
OUT * * LED BO 28 251 2
4001 >Distance Teleprotection ON
(>Dis.Telep. ON)
Teleprotection for
Distance prot.
SP * * LED BI BO
4002 >Distance Teleprotection OFF
(>Dis.Telep.OFF)
Teleprotection for
Distance prot.
SP * * LED BI BO
4003 >Distance Teleprotection BLOCK
(>Dis.Telep. Blk)
Teleprotection for
Distance prot.
SP ON
OFF
ON
OFF
LED BI BO 29 3 1 GI
4005 >Dist. teleprotection: Carrier faulty
(>Dis.RecFail)
Teleprotection for
Distance prot.
SP on
off
* LED BI BO
4006 >Dis.Tele. Carrier RECEPTION
Channel 1 (>DisTel Rec.Ch1)
Teleprotection for
Distance prot.
SP on
off
on LED BI BO 29 6 1 GI
4007 >Dis.Tele.Carrier RECEPTION
Channel 1,L1 (>Dis.T.RecCh1L1)
Teleprotection for
Distance prot.
SP on
off
on LED BI BO 29 7 1 GI
4008 >Dis.Tele.Carrier RECEPTION
Channel 1,L2 (>Dis.T.RecCh1L2)
Teleprotection for
Distance prot.
SP on
off
on LED BI BO 29 8 1 GI
4009 >Dis.Tele.Carrier RECEPTION
Channel 1,L3 (>Dis.T.RecCh1L3)
Teleprotection for
Distance prot.
SP on
off
on LED BI BO 29 9 1 GI
4010 >Dis.Tele. Carrier RECEPTION
Channel 2 (>Dis.T.Rec.Ch2)
Teleprotection for
Distance prot.
SP on
off
on LED BI BO 29 10 1 GI
4030 >Dis.Tele. Unblocking: UNBLOCK
Channel 1 (>Dis.T.UB ub 1)
Teleprotection for
Distance prot.
SP on
off
on LED BI BO 29 30 1 GI
4031 >Dis.Tele. Unblocking: BLOCK
Channel 1 (>Dis.T.UB bl 1)
Teleprotection for
Distance prot.
SP on
off
on LED BI BO 29 31 1 GI
4032 >Dis.Tele. Unblocking: UNBLOCK
Ch. 1, L1 (>Dis.T.UB ub1L1)
Teleprotection for
Distance prot.
SP on
off
on LED BI BO 29 32 1 GI
4033 >Dis.Tele. Unblocking: UNBLOCK
Ch. 1, L2 (>Dis.T.UB ub1L2)
Teleprotection for
Distance prot.
SP on
off
on LED BI BO 29 33 1 GI
4034 >Dis.Tele. Unblocking: UNBLOCK
Ch. 1, L3 (>Dis.T.UB ub1L3)
Teleprotection for
Distance prot.
SP on
off
on LED BI BO 29 34 1 GI
4035 >Dis.Tele. Unblocking: UNBLOCK
Channel 2 (>Dis.T.UB ub 2)
Teleprotection for
Distance prot.
SP on
off
on LED BI BO 29 35 1 GI
4036 >Dis.Tele. Unblocking: BLOCK
Channel 2 (>Dis.T.UB bl 2)
Teleprotection for
Distance prot.
SP on
off
on LED BI BO 29 36 1 GI
4040 >Dis.Tele. BLOCK Echo Signal
(>Dis.T.BlkEcho)
Teleprotection for
Distance prot.
SP on
off
on LED BI BO 29 40 1 GI
4050 Dis. Teleprotection ON/OFF via BI
(Dis.T.on/off BI)
Teleprotection for
Distance prot.
IntSP ON
OFF
* LED BO
4051 Teleprotection is switched ON
(Telep. ON)
Device IntSP * * LED BO 128 17 1 GI
4052 Dis. Teleprotection is switched OFF
(Dis.Telep. OFF)
Teleprotection for
Distance prot.
OUT ON
OFF
* LED BO
F.No. Description Function Type of
Information
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information-No
Data Unit (ASDU)
General Interrogation