4054 Dis. Telep. Carrier signal received
(Dis.T.Carr.rec.)
Teleprotection for
Distance prot.
OUT * * LED BO 128 77 2
4055 Dis. Telep. Carrier CHANNEL FAIL-
URE (Dis.T.Carr.Fail)
Teleprotection for
Distance prot.
OUT * * LED BO 128 39 1 GI
4056 Dis. Telep. Carrier SEND signal
(Dis.T.SEND)
Teleprotection for
Distance prot.
OUT on on LED BO 128 76 2
4057 Dis. Telep. Carrier SEND signal, L1
(Dis.T.SEND L1)
Teleprotection for
Distance prot.
OUT * * LED BO
4058 Dis. Telep. Carrier SEND signal, L2
(Dis.T.SEND L2)
Teleprotection for
Distance prot.
OUT * * LED BO
4059 Dis. Telep. Carrier SEND signal, L3
(Dis.T.SEND L3)
Teleprotection for
Distance prot.
OUT * * LED BO
4060 Dis.Tele.Blocking: Send signal with
jump (DisJumpBlocking)
Teleprotection for
Distance prot.
OUT * * LED BO 29 60 2
4068 Dis. Telep. Transient Blocking
(Dis.T.Trans.Blk)
Teleprotection for
Distance prot.
OUT * ON LED BO 29 68 2
4070 Dis. Tele.Blocking: carrier STOP sig-
nal (Dis.T.BL STOP)
Teleprotection for
Distance prot.
OUT * ON LED BO 29 70 2
4080 Dis. Tele.Unblocking: FAILURE
Channel 1 (Dis.T.UB Fail1)
Teleprotection for
Distance prot.
OUT on
off
* LED BO 29 80 1 GI
4081 Dis. Tele.Unblocking: FAILURE
Channel 2 (Dis.T.UB Fail2)
Teleprotection for
Distance prot.
OUT on
off
* LED BO 29 81 1 GI
4082 DisTel Blocking: carrier STOP sig-
nal, L1 (Dis.T.BL STOPL1)
Teleprotection for
Distance prot.
OUT * * LED BO
4083 DisTel Blocking: carrier STOP sig-
nal, L2 (Dis.T.BL STOPL2)
Teleprotection for
Distance prot.
OUT * * LED BO
4084 DisTel Blocking: carrier STOP sig-
nal, L3 (Dis.T.BL STOPL3)
Teleprotection for
Distance prot.
OUT * * LED BO
4164 Power Swing detected (Power
Swing)
Power Swing OUT ON
OFF
ON
OFF
LED BO 29 164 1 GI
4166 Power Swing TRIP command (Pow.
Swing TRIP)
Power Swing OUT ON ON LED BO 29 166 1
4167 Power Swing detected in L1 (Pow.
Swing L1)
Power Swing OUT ON
OFF
ON
OFF
LED BO
4168 Power Swing detected in L2 (Pow.
Swing L2)
Power Swing OUT ON
OFF
ON
OFF
LED BO
4169 Power Swing detected in L3 (Pow.
Swing L3)
Power Swing OUT ON
OFF
ON
OFF
LED BO
4203 >BLOCK Weak Infeed Trip function
(>BLOCK Weak Inf)
Weak Infeed (Trip
and/or Echo)
SP * * LED BI BO
4221 Weak Infeed Trip fct. is switched
OFF (WeakInf. OFF)
Weak Infeed (Trip
and/or Echo)
OUT ON
OFF
* LED BO 25 21 1 GI
4222 Weak Infeed Trip function is
BLOKKED (Weak Inf. BLOCK)
Weak Infeed (Trip
and/or Echo)
OUT ON
OFF
ON
OFF
LED BO 25 22 1 GI
4223 Weak Infeed Trip function is ACTIVE
(Weak Inf ACTIVE)
Weak Infeed (Trip
and/or Echo)
OUT * * LED BO 25 23 1 GI
4231 Weak Infeed Trip function PICKED
UP (WeakInf. PICKUP)
Weak Infeed (Trip
and/or Echo)
OUT *
OFF
LED BO 25 31 2 GI
F.No. Description Function Type of
Information
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information-No
Data Unit (ASDU)
General Interrogation

Table of Contents