Appendix
B-49
7SA6 Manual
C53000-G1176-C133-1
4414 >Direct Transfer Trip INPUT Phase
L3 (>DTT Trip L3)
DTT Direct Trans-
fer Trip
SP ON
OFF
* LED BI BO
4417 >Direct Transfer Trip INPUT 3ph
L123 (>DTT Trip L123)
DTT Direct Trans-
fer Trip
SP ON
OFF
* LED BI BO
4421 Direct Transfer Trip is switched OFF
(DTT OFF)
DTT Direct Trans-
fer Trip
OUT ON
OFF
* LED BO 51 21 1 GI
4422 Direct Transfer Trip is BLOCKED
(DTT BLOCK)
DTT Direct Trans-
fer Trip
OUT ON
OFF
ON
OFF
LED BO 51 22 1 GI
4432 DTT TRIP command - Only L1 (DTT
TRIP 1p. L1)
DTT Direct Trans-
fer Trip
OUT * ON LED BO 51 32 2
4433 DTT TRIP command - Only L2 (DTT
TRIP 1p. L2)
DTT Direct Trans-
fer Trip
OUT * ON LED BO 51 33 2
4434 DTT TRIP command - Only L3 (DTT
TRIP 1p. L3)
DTT Direct Trans-
fer Trip
OUT * ON LED BO 51 34 2
4435 DTT TRIP command L123 (DTT
TRIP L123)
DTT Direct Trans-
fer Trip
OUT * ON LED BO 51 35 2
6854 >Trip circuit superv. 1: Trip Relay
(>TripC1 TripRel)
Trip Circuit Super-
vision
SP ON
OFF
* LED BI BO
6855 >Trip circuit superv. 1: Breaker
Relay (>TripC1 Bkr.Rel)
Trip Circuit Super-
vision
SP ON
OFF
* LED BI BO
6856 >Trip circuit superv. 2: Trip Relay
(>TripC2 TripRel)
Trip Circuit Super-
vision
SP ON
OFF
* LED BI BO
6857 >Trip circuit superv. 2: Breaker
Relay (>TripC2 Bkr.Rel)
Trip Circuit Super-
vision
SP ON
OFF
* LED BI BO
6858 >Trip circuit superv. 3: Trip Relay
(>TripC3 TripRel)
Trip Circuit Super-
vision
SP ON
OFF
* LED BI BO
6859 >Trip circuit superv. 3: Breaker
Relay (>TripC3 Bkr.Rel)
Trip Circuit Super-
vision
SP ON
OFF
* LED BI BO
6861 Trip circuit supervision OFF (TripC
OFF)
Trip Circuit Super-
vision
OUT ON
OFF
* LED BO
6865 Failure Trip Circuit (FAIL: Trip cir.) Trip Circuit Super-
vision
OUT ON
OFF
* LED BO
6866 TripC1 blocked: Binary input is not
set (TripC1 ProgFAIL)
Trip Circuit Super-
vision
OUT ON
OFF
* LED BO
6867 TripC2 blocked: Binary input is not
set (TripC2 ProgFAIL)
Trip Circuit Super-
vision
OUT ON
OFF
* LED BO
6868 TripC3 blocked: Binary input is not
set (TripC3 ProgFAIL)
Trip Circuit Super-
vision
OUT ON
OFF
* LED BO
7104 >BLOCK Backup OverCurrent I>>
(>BLOCK O/C I>>)
Backup overcur-
rent
SP ON
OFF
* LED BI BO 64 4 1 GI
7105 >BLOCK Backup OverCurrent I>
(>BLOCK O/C I>)
Backup overcur-
rent
SP ON
OFF
* LED BI BO 64 5 1 GI
7106 >BLOCK Backup OverCurrent Ip
(>BLOCK O/C Ip)
Backup overcur-
rent
SP ON
OFF
* LED BI BO 64 6 1 GI
7110 >Backup OverCurrent Instanta-
neousTrip (>O/C InstTRIP)
Backup overcur-
rent
SP ON
OFF
ON
OFF
LED BI BO 64 10 1 GI
7130 >BLOCK I-STUB (>BLOCK I-STUB) Backup overcur-
rent
SP ON
OFF
* LED BI BO 64 30 1 GI
F.No. Description Function Type of
Information
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information-No
Data Unit (ASDU)
General Interrogation

Table of Contents