Appendix
B-50
7131 >Enable I-STUB-Bus function (>I-
STUB ENABLE)
Backup overcur-
rent
SP ON
OFF
ON
OFF
LED BI BO 64 31 1 GI
7151 Backup O/C is switched OFF (O/C
OFF)
Backup overcur-
rent
OUT ON
OFF
* LED BO 64 51 1 GI
7152 Backup O/C is BLOCKED (O/C
BLOCK)
Backup overcur-
rent
OUT ON
OFF
ON
OFF
LED BO 64 52 1 GI
7153 Backup O/C is ACTIVE (O/C
ACTIVE)
Backup overcur-
rent
OUT * * LED BO 64 53 1 GI
7161 Backup O/C PICKED UP (O/C
PIKKUP)
Backup overcur-
rent
OUT *
OFF
M LED BO 64 61 2 GI
7162 Backup O/C PICKUP L1 (O/C
Pickup L1)
Backup overcur-
rent
OUT * ON LED BO 64 62 2 GI
7163 Backup O/C PICKUP L2 (O/C
Pickup L2)
Backup overcur-
rent
OUT * ON LED BO 64 63 2 GI
7164 Backup O/C PICKUP L3 (O/C
Pickup L3)
Backup overcur-
rent
OUT * ON LED BO 64 64 2 GI
7165 Backup O/C PICKUP EARTH (O/C
Pickup E)
Backup overcur-
rent
OUT * ON LED BO 64 65 2 GI
7171 Backup O/C Pickup - Only EARTH
(O/C PU only E)
Backup overcur-
rent
OUT * ON LED BO 64 71 2
7172 Backup O/C Pickup - Only L1 (O/C
PU 1p. L1)
Backup overcur-
rent
OUT * ON LED BO 64 72 2
7173 Backup O/C Pickup L1E (O/C
Pickup L1E)
Backup overcur-
rent
OUT * ON LED BO 64 73 2
7174 Backup O/C Pickup - Only L2 (O/C
PU 1p. L2)
Backup overcur-
rent
OUT * ON LED BO 64 74 2
7175 Backup O/C Pickup L2E (O/C
Pickup L2E)
Backup overcur-
rent
OUT * ON LED BO 64 75 2
7176 Backup O/C Pickup L12 (O/C Pickup
L12)
Backup overcur-
rent
OUT * ON LED BO 64 76 2
7177 Backup O/C Pickup L12E (O/C
Pikkup L12E)
Backup overcur-
rent
OUT * ON LED BO 64 77 2
7178 Backup O/C Pickup - Only L3 (O/C
PU 1p. L3)
Backup overcur-
rent
OUT * ON LED BO 64 78 2
7179 Backup O/C Pickup L3E (O/C
Pickup L3E)
Backup overcur-
rent
OUT * ON LED BO 64 79 2
7180 Backup O/C Pickup L31 (O/C Pickup
L31)
Backup overcur-
rent
OUT * ON LED BO 64 80 2
7181 Backup O/C Pickup L31E (O/C
Pikkup L31E)
Backup overcur-
rent
OUT * ON LED BO 64 81 2
7182 Backup O/C Pickup L23 (O/C Pickup
L23)
Backup overcur-
rent
OUT * ON LED BO 64 82 2
7183 Backup O/C Pickup L23E (O/C
Pikkup L23E)
Backup overcur-
rent
OUT * ON LED BO 64 83 2
7184 Backup O/C Pickup L123 (O/C
Pikkup L123)
Backup overcur-
rent
OUT * ON LED BO 64 84 2
7185 Backup O/C Pickup L123E (O/C
PickupL123E)
Backup overcur-
rent
OUT * ON LED BO 64 85 2
F.No. Description Function Type of
Information
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information-No
Data Unit (ASDU)
General Interrogation

Table of Contents