Cabinet Modules
5.1 Line Connection Modules
Cabinet Modules NEMA
150 Manual, 04/2014, A5E03586450A
Table 5- 12 Technical specifications for Line Connection Modules, 500 to 690 V 3 ph. AC, part II
Infeed/regenerative feedback current
- Line voltage
- Line frequency
V
ACrms
Hz
3 AC 500 -10 % to 3 AC 690 +10 % (-15 % < 1 min)
47 to 63 Hz
1)
- Starting current
A
0.5
0.5
0.5
0.5
0.5
2)
- Option L42/L44
- Option L43
- Option L42/L44
kW
kW
kW
0.29
1.073
0.29
0.41
1.387
0.41
0.6
2.166
0.6
0.6
2.166
0.6
0.95
2.894
0.95
- 230 V AC current demand
- Cooling air requirement
- Sound pressure level L
PA
A
cfm
m
3
/s
dB(A)
1.07
763
0.36
68/70
1.07
763
0.36
68/70
2.14
1526
0.72
70/72
2.14
1526
0.72
70/72
2.14
1526
0.72
70/72
Line connection L1, L2, L3
- Max. conductor cross-section (IEC)
- Max. conductor cross-section (NEC, CEC)
mm
2
AWG/MCM
8 x 240
8 x 500
8 x 240
8 x 500
10 x 240
10 x 500
10 x 240
10 x 500
10 x 240
10 x 500
- Busbar cross-section
- Max. conductor cross-section (IEC)
- Max. conductor cross-section (NEC, CEC)
mm
2
mm
2
PE busbar
600
240
Degree of protection (standard model)
(standard model, IP20)
- width
- height
3)
- depth
- width
- height
3)
inch
inch
inch
mm
mm
23.6
86.6
23.6
600
2200
23.6
86.6
23.6
600
2200
39.4
86.6
23.6
1000
2200
39.4
86.6
23.6
1000
2200
39.4
86.6
23.6
1000
2200
- Option L42, L44
- Option L43
lb
kg
lb
1036
470
1477
1080
490
1499
1323
600
2161
1367
620
2205
1587
720
2381