Chapter 5 Display and Setting of Various Functions
HRL Series 5.4 Description of the Screen
5-39
Table 5.4-11 TEMP READY signal setting
No.
Indication
Item
Setting and selection
Setting range
(1)
High/
Low
Upper/lower
temperature
limit
[High]
Set the temperature range of
the circulating fluid SP.
+0.1 ºC to +10.0 ºC
+1.0 ºC
[Low]
Set the temperature range of
the circulating fluid SP.
-0.1 ºC to -10.0 ºC
-1.0 ºC
(2)
Ready/
Out Time
Stable
temperature
time/extra
time
[Ready]
“TEMP READY” signal is output
when the set time has passed
after the circulating fluid
temperature rises/drops within
the range of (1) “Upper/Lower
temperature limit.
10sec to 9999sec
180sec
[Out Time]
“TEMP READYˮ is cleared
when the set time has passed
after the circulating fluid
temperature rises/drops outside
the range of (1) “Upper/Lower
temperature limit” in the “TEMP
READY” condition.
0sec to 600sec
5sec
(3)
Alarm
Type
AL16 alarm
operation

Disabled
Operation continues during the
alarm
Operation stops during alarm
(4)
Start Time
Start time for
AL16 alarm
monitoring
[Start Time]
Monitoring of “AL16: TEMP
READY alarm” starts when the
set time has passed after the
start of operation.
0sec to 9999sec
600sec
By default
TEMP READY signal (AL16) setting
(1)
(2)
(3)
(4)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRL100-A 40 Series and is the answer not in the manual?

SMC Networks HRL100-A 40 Series Specifications

General IconGeneral
BrandSMC Networks
ModelHRL100-A 40 Series
CategoryChiller
LanguageEnglish

Related product manuals