HRX-OM-X037
Chapter 5 Display and Setting of Various Functions
5.4 Description of the Screen
HRL Series
Table 5.4-10 Settings of AL14/AL15
AL14 : CH2
Circulating fluid
temperature rise
Operation continues during the
alarm
Operation stops during alarm
AL15 : CH2
Circulating fluid
temperature
drop
Operation continues during the
alarm
Operation stops during alarm
Alarm
monitoring
conditions
Continuous monitoring
(monitoring continues even when
the operation stops)
Monitoring continues only during
operation. If [ ] is selected,
[ ] or [ ] should be
selected. Refer to ■ About alarm
monitoring timing (P.5–25) for
details.
No monitoring
time/extra time
Alarm monitoring starts when the
set time has passed after start of
operation.
The alarm is activated when the
set time has passed after the
temperature rises/drops out of the
alarm setting range.
By default.
・TEMP READY alarm (AL16) and TEMP READY function
2. “TEMP READY” signal can be output by signal contact and serial communication if the
circulating fluid temperature is within the range set for the time and temperature.
“TEMP READY” signal cannot be “Disabled”.
[ ] is displayed on the “homeˮ screen if “TEMP READY” conditions are met.
(Refer to 5.4.1 Home screen Operating condition display.)
If the TEMP READY conditions are not met, alarm can be activated as “AL16:TEMP
READY alarm”.This function is OFF (deactivated) by default.
It can be set on “TEMP READY function setting” screen.
Refer to Table 5.4-11 TEMP READY signal setting and ■ About TEMP READY function
(P.5–27) for details.