HRX-OM-X037
Chapter 5 Display and Setting of Various Functions
5.4 Description of the Screen
HRL Series
・Ambient temperature alarm (AL35) and maintenance alarm (AL36)
3. Following alarms can be set for this product:
• AL35: Ambient temperature alarm–– the alarm “AL35” activates when the ambient
temperature value of the product rises/drops out
of the range between 2ºC and 45ºC.
This function is set to “OFFˮ (disabled) by
default.
• AL36: Maintenance alarm–––––––– “Maintenance reminder” can be assigned to
alarm “AL36” as an alarm signal.
This function is set to “Disabled” by default.
Table 5.4-20 Settings for ambient temperature alarm (AL35) and maintenance alarm (AL36)
AL35:
Ambient
temperature
alarm
The alarm activates when
the ambient temperature
sensor is outside of the
range between 2ºC and
45ºC.
Operation
continues during
the alarm
If “WRN” is selected, the
alarm “AL36” activates
when “Maintenance
reminder” is issued.
Operation
continues during
the alarm
By default
Setting for ambient temperature alarm (AL35)
and maintenance alarm (AL36)