HRX-OM-X037
Chapter 8 Control, Inspection and Cleaning
HRL Series 8.1 Quality Control of Circulating Fluid and Facility Water
Chapter 8 Control, Inspection and
Cleaning
8.1 Quality Control of Circulating Fluid and Facility
Water
Table 8.1-1 Quality criteria for clean water (tap water)
Electric conductance
(at 25
o
C)
Acid consumption
(at pH 4.8)
Should not be
detected any
Should not be
detected any
Quoted from the standard “JRA-GL-02-1994”, The Japan Refrigeration and Air Conditioning Industry Association.
Use specified fluids only. If other fluids are used, they may damage the
product, causing fluid leakage, or result in hazards such as electric
shock or leakage of electricity.
When using clear water (tap water), ensure that it satisfies the water
quality criteria shown in the table below.
If the water quality standards are not met, clogging or leakage in the
facility water piping, or other problems such as refrigerant leakage,
etc., may result.
Replace the circulating fluid and/or the facility water if any problems
are found during the regular check. Even if no problems are found,
some of the water in the tank evaporates and impurity concentration in
the circulating fluid increases. Replace the circulating fluid in the tank
once every 3 months. Refer to the section "8.2 Inspection and
Cleaning" for regular inspection.