HRX-OM-X037
Chapter 5 Display and Setting of Various Functions
HRL Series 5.4 Description of the Screen
Table 5.4-3 Screen display of check operation time screen
Displays the operating time for CH1 pump.
Displays the recommended replacement
cycle for CH1 pump.
Displays the operating time for CH2 pump.
Displays the recommended replacement
cycle for CH2 pump.
Displays the operating time for compressor.
Displays the recommended replacement
cycle for a compressor.
Displays the operating time of a fan.
Displays the recommended replacement
cycle for a fan.
Displays the operation time of a chiller.
Displays the usage time of a DI filter.
1 to 9999 hour
By default: 500 hour
The “Maintenance reminder” is issued if the usage
time has reached the hours specified by the user.
Displays the usage time of a DI filter.
1 to 9999hour
By default: 500 hour
The “Maintenance reminder” is issued if the usage
time has reached the hours specified by the user.
Displays the usage time of a dustproof filter.
1 to 9999 hour
By default: 500 hour
The “Maintenance reminder” is issued if the usage
time has reached the hours specified by the user.
Displays the CH2 pump mechanical seal used time
The recommended replacement cycle of the
mechanical seal is displayed.
The operation time is reset to “0 hour” when
[ ] button is pressed.
1 In the case of option D1 "CH1 with electrical conductivity control", to display the value.
2 In the case of option T3 "CH2 High-Pressure Pump Mounted", to display the value.
3 In case of water-cooled type, displayed is "-".
■About “Maintenance reminder” function
・“Maintenance reminder” is displayed on the “Informationˮ screen if a product part in use
has reached its recommended replacement cycle.
・“Maintenance reminder” is always issued if a part of the product has reached the
recommended replacement cycle.
・A “Maintenance reminder” signal can be output by contact signal and by serial
communication.
(Refer to “5.4.10 Communication setting screen” for details.)
・A “Maintenance reminder” signal can be output as “The AL36: Maintenance alarm”.
(Refer to “5.4.9 Function setting screen Ambient temperature alarm [AL35] and
Maintenance Alarm [AL36]”.)