Chapter 5 Display and Setting of Various Functions
HRL Series 5.4 Description of the Screen
5-21
Table 5.4-3 Screen display of check operation time screen
No.
Indication
Item/replacement cycle
Explanation
1
Pump CH1
Operating time
Displays the operating time for CH1 pump.
20000 hour
Displays the recommended replacement
cycle for CH1 pump.
2
Pump CH2
Operating time
Displays the operating time for CH2 pump.
20000 hour
Displays the recommended replacement
cycle for CH2 pump.
3
Compressor
Operating time
Displays the operating time for compressor.
30000hour
Displays the recommended replacement
cycle for a compressor.
4
Fan 3
Operating time
Displays the operating time of a fan.
30000 hour
Displays the recommended replacement
cycle for a fan.
5
Run Time
Operating time
Displays the operation time of a chiller.
6
CH1 DI Filter
1
Operating time
Displays the usage time of a DI filter.
1 to 9999 hour
By default: 500 hour
The Maintenance reminder” is issued if the usage
time has reached the hours specified by the user.
7
CH2 DI Filter
Usage time
Displays the usage time of a DI filter.
1 to 9999hour
By default: 500 hour
The Maintenance reminder” is issued if the usage
time has reached the hours specified by the user.
8
Dustproof
Filter 3
Usage time
Displays the usage time of a dustproof filter.
1 to 9999 hour
By default: 500 hour
The Maintenance reminder” is issued if the usage
time has reached the hours specified by the user.
9
CH2
Mechanical
Seal 2
Operating time
Displays the CH2 pump mechanical seal used time
8000 hour
The recommended replacement cycle of the
mechanical seal is displayed.
10
Reset
[ ] button
The operation time is reset to “0 hour” when
[ ] button is pressed.
1 In the case of option D1 "CH1 with electrical conductivity control", to display the value.
2 In the case of option T3 "CH2 High-Pressure Pump Mounted", to display the value.
3 In case of water-cooled type, displayed is "-".
About “Maintenance reminder” function
“Maintenance reminder” is displayed on the “Informationˮ screen if a product part in use
has reached its recommended replacement cycle.
“Maintenance reminder” is always issued if a part of the product has reached the
recommended replacement cycle.
AMaintenance reminder” signal can be output by contact signal and by serial
communication.
(Refer to “5.4.10 Communication setting screen” for details.)
AMaintenance reminder” signal can be output as “The AL36: Maintenance alarm”.
(Refer to 5.4.9 Function setting screen Ambient temperature alarm [AL35] and
Maintenance Alarm [AL36]”.)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRL100-A 40 Series and is the answer not in the manual?

SMC Networks HRL100-A 40 Series Specifications

General IconGeneral
BrandSMC Networks
ModelHRL100-A 40 Series
CategoryChiller
LanguageEnglish

Related product manuals