EasyManua.ls Logo

SYNAPTICON SOMANET Circulo 7 - Setup of the Safety Functions

Default Icon
1031 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1.3.4.3 Setup of the safety functions
Attention
For SIL 3, PL e, cat.3 it is required to send test pulses from the PLC to the output or to ensure fault
exclusion for wiring “Short circuit between any two conductors” according to ISO 13849-2:2012
between signals STO-SBC 1 and STO-SBC 2
permanently connected (fixed) and protected against external damage, e.g. by cable ducting,
armouring, OR
separate multicore cables, OR
within an electrical enclosure, OR
individually shielded with earth connection.
Synapticon Documentation
© 2021 Synapticon GmbH | Daimlerstraße 26 | D-71101 Schönaich Documentation v 4.19.0 | Built 2022-02-01 196/1031

Table of Contents

Related product manuals