Instruction Manual
March 2010
TR200
BAS-SVX19C-EN
BAS-SVX19C-EN
Trane has a policy of continuous product and product data improvement and reserves the
right to change design and specifications without notice.
www.trane.com
For more information, contact your local Trane
office or e-mail us at comfort@trane.com
Literature Order Number BAS-SVX19C-EN
Date March 2010
Supersedes August 2009

Table of Contents

Other manuals for Trane TR200

Questions and Answers

  • N
    Nicholas YoungAug 21, 2025
    How to fix a dark display on Trane TR200?
    • J
      John Barrett Jr.Aug 21, 2025
      If the display is dark or not functioning on your Trane DC Drives, several issues could be the cause. First, check the input power source. Also inspect the fuses and circuit breaker. Ensure the LCP is correctly connected and not faulty; if it is, replace the LCP or connection cable. Verify that there are no shortcuts on the control voltage terminals and that they are properly wired. Confirm you are using the correct LCP (LCP 101 (P/N 130B1124) or LCP 102 (P/N 130B1107)). Adjust the contrast by pressing [Status] + [?]/[?]. If none of these steps work, the display (LCP) or internal voltage supply might be defective, and you should contact your supplier.
  • E
    Erik WhiteSep 4, 2025
    Why is the motor not reaching maximum speed on Trane TR200?
    • M
      Marc GonzalesSep 4, 2025
      If the motor is not reaching its maximum speed on your Trane DC Drives, it could be due to frequency limits set incorrectly. Program the correct limits. Alternatively, the reference input signal may not be scaled correctly; in this case, program the correct settings.
  • S
    Sherry MyersSep 2, 2025
    How to reverse motor direction on Trane TR200 DC Drives?
    • A
      Andrew BrownSep 2, 2025
      If the motor is running in the wrong direction on your Trane DC Drives, it could be due to a motor rotation limit. Program the correct settings. Another cause might be an active reversing signal; deactivate the reversing signal. Check the motor phase connection.
  • T
    timothythomasSep 1, 2025
    What causes motor current imbalance greater than 3% in Trane TR200?
    • R
      Robert GriffinSep 1, 2025
      A motor current imbalance greater than 3% in Trane DC Drives can be caused by a problem with the motor or its wiring. If the imbalanced leg follows the wire, check the motor and motor wiring. If the imbalance remains on the same output terminal, it indicates a problem with the frequency converters; in this case, contact the supplier.
  • M
    Mary DavisAug 30, 2025
    How to troubleshoot mains current imbalance greater than 3% in Trane DC Drives?
    • F
      Felicia CampbellAug 31, 2025
      If you observe a mains current imbalance greater than 3% in your Trane DC Drives, the problem might stem from the mains power supply itself. Check the mains power supply. If the imbalance follows the wire, it is a power problem. Alternatively, the issue could be with the frequency converter. If the imbalance stays on the same input terminal, contact the supplier.
  • K
    Kimberly RochaAug 29, 2025
    What to do if Trane DC Drives power fuses open or circuit breaker trips?
    • R
      rrubioAug 29, 2025
      If the power fuses are open or the circuit breaker trips in your Trane DC Drives, it could be due to a phase-to-phase short. Eliminate any shorts that you detect. Another cause could be motor overload, so review the specifications for the application. Loose connections may also cause this issue, so tighten any loose connections you find.
  • B
    Brittney PerezAug 27, 2025
    Why do overload trips occur in Trane TR200 DC Drives?
    • A
      amandamercadoAug 28, 2025
      If your Trane DC Drive overloads trip, this can occur for several reasons. The motor might be overloaded, so try reducing the load. Loose connections can also cause this issue; perform a pre-startup check, tighten any loose connections, and replace any overheated components or wires. Finally, ensure that the OL (Overload) is set correctly for the motor's current.
  • J
    James KramerAug 27, 2025
    What to do if my Trane DC Drives has repeated fuse or circuit breaker fault?
    • C
      Charles SteinAug 27, 2025
      If your Trane DC Drive experiences repeated fuse or circuit breaker faults, it could stem from several factors. The load on the motor might be too high, so reducing it could resolve the issue. There may be a problem with the power supply itself, so correct any problems found. A motor problem could also be the cause, in which case you should repair or replace the motor.
  • S
    Steven JohnsonAug 25, 2025
    Why does my Trane TR200 DC Drives have no function?
    • C
      Cheyenne AyersAug 26, 2025
      If your Trane DC Drive has no function, several issues could be the cause. First, ensure the correct voltage is supplied at the source. Check for any missing or open fuses, or tripped circuit breakers, and reset them if necessary. Inspect the panel for loose connections and tighten them. Verify all customer connections are properly made or jumpers are installed, paying special attention to the customer interlock. Ensure customer wires are correctly terminated and that the correct voltage is applied. Also, check that the power connections are correct and the power disconnect is not open. Finally, make sure the operator switches are in the correct position and the OL (Overload) hasn't tripped; perform the pre-startup checklist and set the OL per the instructions.
  • G
    Gary MackAug 23, 2025
    Why is the motor not running on my Trane TR200 DC Drives?
    • S
      sharonnguyenAug 23, 2025
      If the motor is not running on your Trane DC Drives, consider the following possible causes: - The service switch may be open, or there may be a missing motor connection. Connect the motor and check the service switch. - If using a 24 V DC option card, there may be no mains power. Apply mains power to run the unit. - The LCP may be stopped. Press [Auto On] or [Hand On] to run the motor. - There may be a missing start signal. Apply a valid start signal to start the motor. - The motor coast signal may be active. Apply 24 V on terminal 27 or program this terminal to No operation. - The reference signal source may be incorrect. Program correct settings and check wiring and scaling of terminals.

Summary

Safety

Warnings, Cautions and Notices

Explains the meaning of warnings, cautions, and notices for safety.

High Voltage Warning

Details hazards associated with high voltage and necessary safety precautions.

Warning against Unintended Start

Warns about potential unintended motor starts and necessary precautions.

Before Commencing Repair Work

Provides a checklist of safety steps before starting repair work on the unit.

Mechanical Installation

Before Starting

Provides a checklist for unpacking and identifying the frequency converter unit.

How to Install

Shows mechanical front views of different enclosure types and mounting hole information.

Mechanical Mounting

Details requirements for side-by-side installation and air passage for different enclosures.

Electrical Installation

Fuse Selection for Drives with Internal Drive Fusing

Shows locations of input power, motor power, and relay terminals for drives with internal fusing.

Fuse Replacement Table

Provides a table listing fuse ratings for various drive ratings and voltages.

How to Connect Motor - Introduction

Provides an introduction to motor connection, including cable requirements and precautions.

How to Test Motor and Direction of Rotation

Provides step-by-step instructions for testing motor connection and direction of rotation.

How to Operate the Frequency Converter

How to Connect a PC to the Frequency Converter

Guides on connecting a PC for control or programming using USB or RS-485 interfaces.

Initialization to Default Settings

Describes two methods for initializing the frequency converter to default settings: recommended and manual.

How to program the Frequency Converter

Quick Menu Mode

Explains how to set parameters using the Quick Menu button and provides an example.

Efficient Parameter Set-up for TR200 Applications

Details how to use the Quick Setup option for efficient parameter configuration, including an example.

Function Set-ups

Explains how to access Function Set-ups for quick parameter access and provides examples.

Parameter Set-Up

Introduces parameter setup groups and their functions.

Main Menu Mode

Accesses the main menu mode for parameter group selection and editing.

Troubleshooting

Alarms and Warnings

Explains how warnings and alarms are signalled and how to reset tripped alarms.

Alarm;Warning Code List

A comprehensive list of alarm/warning codes, their descriptions, and associated parameters.

Fault Messages

Details various fault messages, their causes, and troubleshooting steps.