Product Description
TITANUS
MICRO·SENS
®
18
06/13
Airflow monitoring is temperature-compensated and can be set to be air
pressure-dependent.
Installation and commissioning of the TITANUS
MICRO·SENS
®
are simple
with the Plug & Play function.
The device base is pre-assembled on site. By pre-setting the detection unit
for standard applications, the TITANUS
MICRO·SENS
®
is operational imme-
diately after it is inserted in the device base.
For maximum safety, the TITANUS
MICRO·SENS
®
can be fitted with redun-
dancy ventilators as an option. During operation of the device with the re-
dundancy ventilator, ROOM•IDENT is not possible.
Fitted with a network card, several TITANUS
MICRO·SENS
®
devices can be
linked together in an Ethernet network. From a central point the user can, for
example, via Visu
LAN
T
®
monitor the whole plant for smoke levels, airflow
values etc. In addition, the TITANUS
MICRO·SENS
®
can be integrated via
the so-called OPC server into existing hazard and building management sys-
tems.
The TITANUS
MICRO·SENS
®
has one potential free contact each for alarm
and fault So the smoke detection system can be switched to collective and
addressable (Via the address module of the particular FAS) recording lines
of any central fire alarm systems (FAS). A relay card (optional) can be con-
nected to the TITANUS
MICRO·SENS
®
in order to connect the potential-free
contact for the pre-alarm to a detector line of a CFDU.
With the DIAG 3 diagnostics device, there is a system available for commis-
sioning, inspection and servicing which makes it possible to configure the
device quickly and easily and contain faults. For diagnostics purposes
events are stored in the TITANUS
MICRO·SENS
®
for 72 hours.
The monitoring surfaces of the detection point type for the TITANUS
MI-
CRO·SENS
®
are to be set to match the point-specific smoke alarms. The de-
tection points can thus be designed similar to point-specific smoke alarms in
accordance with the particular national regulations.
Plug and Pla
y
Redundancy ventilators
Network capacit
y
Potential free contacts
Diagnostics
Designing detection points

Table of Contents