TITANUS
MICRO·SENS
®
Installation
06/13
135
Delay time for air flow fault
If you want to change the delay time for forwarding an air flow fault, this can
be done by using the diagnostic tool for TITANUS
MICRO·SENS
®
.
Fault
delay
Fault
delay
Standard
Settings
stages
Detection Unit
DM-TM-10
1 s – 60 min
100 s
1 s
Detection Unit
DM-TM-50
1 s – 60 min
100 s
1 s
The standard delay time setting is 100 seconds. In areas with time-limited
fault variables (e.g. air pressure oscillations), then depending on the duration
of the fault variables, other delay times should be set.
Action-Alarm Threshold
Action-Alarm threshold changes for „Fire alarm after ROOM·IDENT“ can be
carried out by the diagnostic tool for TITANUS
MICRO·SENS
®
.
Action
alarm
Action
alarm
Standard
Settings
stages
Detection Unit
DM-TM-10
10 – 80 %
60 %
1 %
Detection Unit
DM-TM-50
10 – 80 %
60 %
1 %
Default value for action-alarm threshold is set to 60% of the fire alarm
threshold.
6.12.1.4
6.12.1.5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WAGNER Titanus Micro-Sens and is the answer not in the manual?

WAGNER Titanus Micro-Sens Specifications

General IconGeneral
BrandWAGNER
ModelTitanus Micro-Sens
CategorySmoke Alarm
LanguageEnglish

Related product manuals