TITANUS
MICRO·SENS
®
Commissioning
06/13
171
Air Pressure-Independent Adjustment
Air pressure-independent adjustment for the TITANUS
MICRO·SENS
®
hap-
pens completely automatically each time the detection unit is inserted into
the device base and the Jumper X4 is changed or via the diagnostics tool.
During the learning phase, the alarm detection is fully functional. During this
time the operating display flashes and there must be no air flow influences.
When initialising is completed, the operating display changes to a permanent
light and the air flow sensor has determined its ideal value for the connected
pipe system.
Air Pressure-Dependent Adjustment
This kind of adjustment can only be carried out by using the diagnostics tool.
A barometer (Recommended: Digital precision pocket barometer GPB 1300,
Greisinger electronic GmbH) is required for air pressure-dependent adjust-
ment of the air flow sensor. The following steps must be taken:
1. Press the “Settings” button so that you can change the figures in the di-
agnostics tool on the “Settings” screen.
8.3.1
8.3.2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WAGNER Titanus Micro-Sens and is the answer not in the manual?

WAGNER Titanus Micro-Sens Specifications

General IconGeneral
BrandWAGNER
ModelTitanus Micro-Sens
CategorySmoke Alarm
LanguageEnglish

Related product manuals