Commissioning
TITANUS
MICRO·SENS
®
172
06/13
2. Determine the height above sea level (NN) at the aspirating smoke de-
tection system installation site and enter it in the “Settings“ screen.
3. 3. Using a hand-held barometer, measure the air pressure and enter this
figure in the “Settings” screen in the diagnostics tool as well.
NOTICE
If this measured air pressure does not correspond to the annual average
for that height, then the air flow sensor will not adjust to 0 %.
4. Press the “Initialise” button.