EasyManua.ls Logo

WAGNER Titanus Micro-Sens - 7.10 Steam Trap Installation

WAGNER Titanus Micro-Sens
238 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TITANUS
MICRO·SENS
®
Installation Pipe System
06/13
161
Steam trap
Steam trap type KA-DN-25
Figure 102: Mounting of the steam trap type KA-DN-25 to the pipe system
Install the steam trap at the lowest point of the pipe system behind the air fil-
ter and TITANUS
®
- device and fasten it with PG screw joints.
NOTICE
Two 45º elbows are required on each connection end for the installation of
the steam trap to the pipe system.
When installing the steam trap, note the direction of air flow (see arrow on
housing of steam trap).
1. Prepare the pipe system with two 45° elbows at each end of the steam
trap and connect it to the PG screw joints.
2. Additionally, secure the steam trap with two screws and the support.