Installation
TITANUS
MICRO·SENS
®
136
06/13
Fault display
The displaying of collective fault (air flow and detection unit fault) can, as
preferred, be set to storing or not storing (standard). This is activated or de-
activated by using the diagnostic tool for TITANUS
MICRO·SENS
®
.
Fault storing Fault not storing
Standard
Detection Unit
DM-TM-10
off – on
off
Detection Unit
DM-TM-50
off – on
off
Dynamic air flow
The dynamic air flow is activated or deactivated by using the diagnostic tool
for TITANUS
MICRO·SENS
®
.
Dynamic air flow Dynamic air flow
Standard
Detection Unit
DM-TM-10
off – on
off
Detection Unit
DM-TM-50
off – on
off
ROOM·IDENT
Location of a fire is activated or deactivated by using the diagnostic tool for
TITANUS
MICRO·SENS
®
.
ROOM·IDENT ROOM·IDENT
Standard
Detection Unit
DM-TM-10
off – on
off
Detection Unit
DM-TM-50
off – on
off
6.12.1.6
6.12.1.7
6.12.1.8