Technical Description
TITANUS
MICRO·SENS
®
48
06/13
Air filters for dusty areas
Figure 28: TITANUS MICRO•SENS
®
with air filter
In areas with interference to the environment such as, e.g. dust, an air filter
is to be used to protect the smoke detection system.
The standard air filter used is the type LF-AD-x, consisting of a plastic hous-
ing with two pipe connections, used. The air filter is automatically monitored
for dirt (blockage) by the TITANUS
MICRO·SENS
®
air flow monitoring ar-
rangement. If the air filters are dirty, then the filter inserts must be changed
by opening the filter housing.
In extremely dusty areas (e.g. recycling plants) in which the use of an LF-AD
is not sufficient, a special filter must be used. The special filter safely holds
back the dust particles in a heavily polluted atmosphere using the filter me-
dium. The filter is guaranteed to have an even quality of dust collection right
through to the end of its useful life. Two types of special filter are available
(type SF-400 and type SF-650), the SF-650 having a longer useful life be-
cause of its larger surface area.
3.3.4
Type LF-AD-x air filte
r
Special type SF-x filte
r

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WAGNER Titanus Micro-Sens and is the answer not in the manual?

WAGNER Titanus Micro-Sens Specifications

General IconGeneral
BrandWAGNER
ModelTitanus Micro-Sens
CategorySmoke Alarm
LanguageEnglish

Related product manuals