Maintenance
TITANUS
MICRO·SENS
®
188
06/13
Testing pipe system
Test the aspiration apertures on the pipe system for blockage, in areas in
which dust particles or icing may be found. If necessary, blow the pipe sys-
tem and aspiration apertures free with compressed air. Use a portable com-
pressed air bottle to do this (blow through device) or press the manual blow
through equipment installed on site.
WARNING
Before blowing through the pipe system, separate the TITANUS
MI-
CRO·SENS
®
from the pipe system, as otherwise the air flow sensor will be
damaged.
9.3