TITANUS
MICRO·SENS
®
Installation Pipe System
06/13
163
Test adapter
Figure 104: Installing the test adapter in the pipe system
The test adapter is stuck into the pipe system immediately next to the air
sampling smoke detection system. The test adapter must always be closed
during normal operation and is only opened for maintenance and service
purposes, to introduce test gas or smoke.
WARNING
After testing detection in the air sampling smoke detection system and
alarm forwarding, the test adapter must be closed again, otherwise there
will be an air flow fault!