TITANUS
MICRO·SENS
®
Maintenance
06/13
191
Changing the filter on the type LF-AD-x air filter
Figure 110: Changing the filter Inserts
To clean or change the filter inserts, proceed as follows:
1. Loosen the four screws and remove the housing cover.
2. Remove the filter inserts and check them visually for dust. If slightly dirty,
the filter inserts can be cleaned. If they are very dirty, they must be
changed.
3. Clean the housing inner carefully of all dust deposits. Now insert the
cleaned or new filter inserts in the correct order. The correct sequence is
shown on the information plate on the housing base.
4. Replace the housing cover and screw it down again.