EasyManuals Logo

WAGNER Titanus Micro-Sens User Manual

WAGNER Titanus Micro-Sens
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #138 background imageLoading...
Page #138 background image
Installation
TITANUS
MICRO·SENS
®
138
06/13
Fan voltage Fan voltage
Standard
Settings
stages
Detection Unit
DM-TM-10
9 V – 13.5 V
9 V
0.1 V
Detection Unit
DM-TM-50
9 V – 13.5 V
9 V
0.1 V
WARNING
If the TITANUS
MICRO·SENS
®
fan voltage is changed, the device auto-
matically carries out air flow initialisation.
Inputting the current air pressure
The current air pressure for the monitoring area must be input by using the
TITANUS
MICRO·SENS
®
diagnostic tool if air pressure-dependent adjust-
ment is required.
The standard setting is 1013 hPa, corresponding to the average air pressure
at sea level.
Inputting height above Normal Sea Level (NN)
The figure for the height above normal sea level is that for the installation
site of the TITANUS
MICRO·SENS
®
above sea level. The figure is input by
using the diagnostic tool. The standard setting is 0 m. The figure has to be
changed if the device’s air flow sensory analysis has to be balanced be-
cause of the air pressure (see chapter commissioning).
WARNING
If the standard setting for air pressure or the height above sea level is
changed, the TITANUS
MICRO·SENS
®
air flow is automatically re-
initialised.
6.12.1.12
6.12.1.13

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WAGNER Titanus Micro-Sens and is the answer not in the manual?

WAGNER Titanus Micro-Sens Specifications

General IconGeneral
BrandWAGNER
ModelTitanus Micro-Sens
CategorySmoke Alarm
LanguageEnglish

Related product manuals