Design
TITANUS
MICRO·SENS
®
98
06/13
Power supply
The alarm-ready status in the fire protection system and the aperture of an
alarm are taken into account when rating the external mains supply. In the
system's alarm-ready status, the mains supply must supply standby current
to the air sampling smoke detection systems and ensure that the emergency
power batteries are charging in accordance with DIN VDE 0833 Part 1 (80%
load in 24 hours).
NOTICE
The mains supply of the air sampling smoke detection systems shall be
approved according to EN 54-4.
The following formulae apply in case of alarm:
.max,supmaxmax.,
)(
plypowerareaquiescentareaalarmroomtotal
InnInII
powerquie
centalarmequipmenttotal
nn
n
I
.max
)(
The current for charging the accus is calculated by the following formula:
24
8,0
min
arg
alno
in
ch
K
max.y,
owersu
lcharging,
n
I
quie
centequipmenttotal
I
total
= total current of all connected air sampling systems [A]
I
ower su
l
, max.
= max. supply current of the power supply unit [A]
n = total number of all air sampling systems connected to a power
supply unit
N
max. area
= total number of all air sampling systems in the area with the
highest power consumption
I
alarm
= alarm current of an air sampling system [A]
I
uiescent
= quiescent current of an air sampling system [A]
K
nominal
= nominal capacity of the accumulators [Ah]
I
charging
= charging current of the accumulators (within 24 h 80% of the
nominal capacity) [A]
5.4
Power calculation
Room protection
Equipment protection
Charging current