TITANUS
MICRO·SENS
®
Technical Data
06/13
55
Technical Data
NOTICE
All power consumption figures relate to an ambient temperature of 20°C.
TITANUS
MICRO·SENS
®
TITANUS MICRO·SENS
®
Power supply (Ue)
Nominal power supply
16 - 30 V DC
24 V DC
U
L
1= 9 V
(at 24 V)
U
L
1= 10.5 V
(at 24 V)
U
L
1= 12 V
(at 24 V)
U
L
1= 13.5 V
(at 24 V)
Starting current (1) 150 mA
Power consumption at idle status (1) 105 mA 125 mA 145 mA 170 mA
Power consumption at alarm
status(1)
Device variant without smoke level
110 mA
130 mA
150 mA
175 mA
Power consumption at alarm
status(1)
Device variant with smoke level
140 mA
160 mA
180 mA
205 mA
(1) (without extra modules) U
L
= Fan voltage
Contact loading capacity of the
alarm and fault relay
1A / 30 VDC
Dimension (H x W x D mm) 70 x 140 x 222 mm
Weight 0.8 kg
L
pa
according to EN ISO 3744, 1995 at 40 dB(A)