Technical Description
TITANUS
MICRO·SENS
®
54
06/13
The TITANUS
MICRO·SENS
®
is used in environments with high humidity
condensate can occur in the air sampling system. In order to collect this
condensate the steam trap is installed at the deepest point of the pipe sys-
tem before the air filter and the air sampling smoke detection system. The
45°-elbows permit an optimum distance to the wall.
The steam trap can be operated in a temperature range between 0°C and
+50°C. The sinter filter in the steam trap has a pore width of 50 µm and ab-
sorbs also coarse dirt particles.
The steam trap is used in the following areas:
Areas with severely oscillating temperatures and high air humidity
External areas