TITANUS
MICRO·SENS
®
Installation Pipe System
06/13
143
NOTICE
After pipe installation is complete, check for the following:
- air tightness (e.g. due to damage)
- any faulty connections
- correct projection of the aspiration aperture
Mounting air sampling hose
The air sampling hose should be used in compliance with the design guide-
lines (see chapter "Design").
1. Cut the air sampling hose with a pipe cutter or a metal saw. Chips must
be removed and rough edges trimmed.
2. Before gluing, remove any dirt and grease from the joints with the rec-
ommended cleaning agent. Glue the hose ends to the corresponding fit-
tings so that they are airtight.
air sampling
hose halogen
free
Air sampling
hose (PVC)
Cleaning agent Adhesive Pipe cutter
SCH-PG16 SCH-P-25 Tangit cleaner Tangit adhesive Pipe cutter
or
38 mm
saw
WARNING
Adhesives and cleaning products contain solvents and are flammable. It is
essential to observe the supplier’s safety information before processing.
Glue the air sampling hose as follows:
Stick the air sampling hose by ABS glue into the hose bolting type SCH-PG-
16-VO. Turn the hose bolting into the specified pipe with female thread type
ABSR-2518-PG16.
Stick the air sampling hose by ABS glue into pipe fittings respectively
sleeves of a pipe system with 25 mm external diameter.
7.1.2
Type SCH-PG16
Type SCH-P-25