TITANUS
MICRO·SENS
®
Commissioning
06/13
165
Commissioning
NOTICE
At commissioning, the test record should generally be stored in DIAG 3.
This is required for later assessment of data such as the air flow figure,
type of adjustment (see Chapter 8.1), commissioning temperature, air
pressure and height above sea level.
Commissioning the detection unit
Before the detection unit is used, the pipe system must be installed in full, be
operational and be connected to the TITANUS
MICRO·SENS
®
device base.
Figure 105: Check whether the pipe system is correctly connected
At commissioning, the TITANUS
MICRO·SENS
®
detection unit is to be in-
serted in the pre-mounted device base which has been checked to ensure it
is correctly wired.
NOTICE
When inserting the detection unit, take note of the mechanical coding which
protects the device against twisting.