Commissioning
TITANUS
MICRO·SENS
®
180
06/13
3. The correct aspiration reducing films have been stuck to the aspiration
apertures.
NOTICE
After the air flow sensor is adjusted (section "Air Flow Sensor Adjustment ")
no more changes should be made to the pipe system.
If changes are necessary later, the air flow sensor must be adjusted again.
After function tests are completed, the device and the pipe system must be
re-commissioned from section "Air Flow Sensor Adjustment.
NOTICE
After commissioning is completed, the settings should be recorded using
the diagnosis tool and stored. A print-out of the settings should be filed with
the project documents for subsequent follow-up work.