EasyManuals Logo

WAGNER Titanus Micro-Sens User Manual

WAGNER Titanus Micro-Sens
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #184 background imageLoading...
Page #184 background image
Commissioning
TITANUS
MICRO·SENS
®
184
06/13
The aspiration point for which the transport time is to be determined is now
selected by clicking. For each aspiration point selected, the pre-selected
time required for reaching the aspiration point and providing the smoke must
be entered. When the pre-selected time has lapsed, the particular smoke de-
tection point must be charged with smoke. There must be smoke at the aspi-
ration point for another 10 to 15 seconds after the pre-selected time has
lapsed.
Before starting to determine the transport time, check by using a bargraph
(smoke level) that there is no smoke in the aspiration pipe.
After starting to determine the transport time, the learn mode is active and
TITANUS
MICRO·SENS
®
switches to blowing out the aspiration pipe. The
display for the aspiration point in question is yellow.
After the pre-selected time has lapsed, the TITANUS
MICRO·SENS
®
switches to aspirate. At this point, there must be smoke at the aspiration
point selected.
If the TITANUS
MICRO·SENS
®
detects the smoke, the smoke level indicates
this. The display for the aspiration point selected goes green and the time
determined is entered.
The learn mode for the aspiration point selected is thereby closed.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WAGNER Titanus Micro-Sens and is the answer not in the manual?

WAGNER Titanus Micro-Sens Specifications

General IconGeneral
BrandWAGNER
ModelTitanus Micro-Sens
CategorySmoke Alarm
LanguageEnglish

Related product manuals