Name LCD Display Description Values Page
F7-20
(3F8)
EtherNet/IP Power
Scaling Factor
EN Power Scale
Sets the scaling factor for the power monitor in EtherNet/IP
Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-21
(3F9)
EtherNet/IP Voltage
Scaling Factor
EN Voltage Scale
Sets the scaling factor for the voltage monitor in EtherNet/IP
Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-22
(3FA)
EtherNet/IP Time
Scaling
EN Time Scale
Sets the scaling factor for the time monitor in EtherNet/IP Class
ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-23 to
F7-32
(3FB to
374)
Dynamic Output
Assembly Parameters
Parameters used in Output Assembly 116. Each parameter
contains a MEMOBUS/Modbus address. The value received
for Output Assembly 116 will be written to this corresponding
MEMOBUS/Modbus address. A MEMOBUS/Modbus address
value of 0 means that the value received for Output Assembly
116 will not be written to any MEMOBUS/Modbus register.
Default: 0
F7-33 to
F7-42
(375 to
37E)
Dynamic Input
Assembly Parameters
Parameters used in Input Assembly 166. Each parameter
contains a MEMOBUS/Modbus address. The value sent for
Input Assembly 166 will be read from this corresponding
MEMOBUS/Modbus address. A MEMOBUS/Modbus address
value of 0 means that the value sent for Input Assembly 166 is
not defined by the user, therefore the option default register
value will be returned.
Default: 0
<1> When using this setting, be sure to take safety measures, such as installing an emergency stop switch. The drive will continue to operate when a
fault is detected.
<2> Available in drive software versions PRG: 1017 and later.
<3> Available in drive software versions PRG: 1018 and later.
<4> If the RUN command is maintained during the alarm condition, the drive will accelerate back to the frequency reference when the Communications
Error condition is resolved.
<5> Parameter setting value is not reset to the default value when the drive is initialized.
<6> Cycle power for setting changes to take effect.
<7> When setting F7-13 to 0, all IP addresses (F7-01 to F7-04) must be unique.
<8> When setting F7-13 to 0, also set parameters F7-01 to F7-12.
<9> When F7-14 is set to 0 or 2, be sure to also set F7-15.
<10> Default is 0 and range is 0 to 300 in drive software versions PRG: 1017 and earlier.
B.6 F: Communication Option Parameters
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
301