Wire Gauge
Terminal
Screws
Crimp Terminal
Model Number
Tool
Insulation
Cap
Model No.
Code
<1>
Machine No. Die Jaw
14 mm
2
6 AWG
M5 R14-5 YA-4 AD-902 TP-014 100-054-034
M8 R14-8 YA-5 AD-952 TP-014 100-054-035
22 mm
2
4 AWG
M5 22-5NS YA-5 AD-953 TP-022 100-051-262
M8 R22-8 YA-5 AD-953 TP-022 100-051-263
30 / 38 mm
2
3 / 2 AWG
M8 R38-8 YA-5 AD-954 TP-038 100-051-264
50 / 60 mm
2
1 AWG
1/0 AWG
1/0 AWG × 2P
M8 R60-8 YA-5 AD-955 TP-060 100-051-265
70 mm
2
2/0 AWG
2/0 AWG × 2P
M8
CB70-S8
YF-1 YET-300-1 TD-322,TD-311 TP-080
100-064-417
70-8 100-064-250
M10 70-10 YF-1 YET-300-1 TD-322,TD-311 TP-080 100-064-251
80 mm
2
3/0 AWG × 2P
3/0 AWG × 4P
M10 80-10 YF-1 YET-300-1 TD-323,TD-312 TP-080 100-051-267
M12 80-L12 YF-1 YET-300-1 TD-323,TD-312 TP-080 100-051-558
100 mm
2
4/0 AWG × 2P
4/0 AWG × 4P
M12 100-L12 YF-1 YET-300-1 TD-324,TD-312 TP-100 100-051-560
150 mm
2
250 kcmil × 2P
300 kcmil × 2P
M12 150-L12 YF-1 YET-300-1 TD-325,TD-313 TP-150 100-051-562
<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.
Example 1: Models with 300 kcmil for both input and output require one set for input terminals and one set for output terminals, so the user should
order two sets of [100-051-272].
Example 2: Models with 4/0 AWG × 2P for both input and output require two sets for input terminals and two sets for output terminals, so the user
should order four sets of [100-051-560].
Note: Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable
temperature of 75 °C 600 Vac UL-approved vinyl-sheathed insulation.
n
Factory Recommended Branch Circuit Protection
WARNING! Fire Hazard. Install adequate branch circuit protection according to applicable local codes and this manual. Failure to comply
could result in fire and damage to the drive or injury to personnel. The device is suitable for use on a circuit capable of delivering not more
than 100,000 RMS symmetrical amperes, 240 Vac (200 V class) and 480 Vac (400 V class), when protected by branch circuit protection
devices specified in this manual.
Branch circuit protection shall be provided by any of the following: Non-time delay Class J, T, or CC fuses sized at 300% of the drive input
rating, or Time delay Class J, T, or CC fuses sized at 175% of the drive input rating, or MCCB sized at 200% maximum of the drive input
rating.
Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C.
Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in Table 6.3.
Table D.4 Factory Recommended Z1000 AC Drive Branch Circuit Protection
Model
Nominal Output
Power (HP)
AC Drive Input
(A)
MCCB Rating (A)
<1>
Time Delay Fuse
Rating (A)
<2>
Non-time Delay
Fuse Rating (A)
<3>
Bussmann
Semiconductor
Fuse Model
(Fuse Ampere)
<4>
Three-Phase 200 V Class
2A0011 3 10.6 20 17.5 30 FWH-40B (40)
2A0017 5 16.7 30 25 50 FWH-50B (50)
2A0024 7.5 24.2 40 40 70 FWH-80B (80)
2A0031 10 30.8 60 50 90 FWH-100B (100)
2A0046 15 46.2 90 80 125 FWH-150B (150)
2A0059 20 59.4 110 100 175 FWH-175B (175)
2A0075 25 74.8 150 125 200 FWH-225A (225)
2A0088 30 88 175 150 250 FWH-225A (225)
2A0114 40 114 225 175 300 FWH-250A (250)
D.3 UL/cUL Standards
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
373