Bit-0toBit-2ofManualPresetOutputNumber(MP.B0toMP.B2)
The manual preset output number can be switched using contact input. There are two
methods to specify a manual preset output number.
• Status switch 1 (Operation by keystroke or via communication is enabled depending
on the conditions.)
Manual preset
outputnumber
Contact status
MP.B2 MP.B1 MP.B0
1 OFF OFF ON
2 OFF ON OFF
3 OFF ON ON
4 ON OFF OFF
5 ON OFF ON
*1:
“1” when the contact input is turned on and “0” when turned of
f.
*2:
Manual preset output number can be switched by keystroke via comm
unication when all contact
inputs of MP
.B0 to MP.B2 are turned off.
*3: Manual preset output number cannot be switched by keystroke or via communication when any
contact input of MP.B0 to MP.B2 is turned on.
*4:
The contact input is turned off when the bit of manual preset output number is not assigned to
the contact input.
• Status Switch 2 (Operation by keystroke or via communication is disabled.)
Manual preset
outputnumber
Contact status
MP.B2 MP.B1 MP.B0
1 OFF OFF OFF
2 OFF OFF ON
3 OFF ON OFF
4 OFF ON ON
5 ON OFF OFF
*1: “1” when contact input is turned on and “0” when turned off.
*2: The contact input is turned off when the bit of manual preset output number is not assigned to
the contact input.
In Cascade control, the manual preset output number selection is only for Loop 2.
Setting Details
Parameter
symbol
Name
Display
level
Setting range Menusymbol
MP.BC
Bit changing method of
manual preset output
number
PRO
0: Status switch 1
1: Status switch 2
DI.NU
Note1: In Cascade control, the LP2 lamp is lit while the Loop-2 parameter is displayed.
12.1 Setting Contact Input Function