18-25
IM 05P01C31-01EN
Parameters
18
OutputSettingMenu(Menu:OUT)(Continuedfrompreviouspage)
Parameter
symbol
Name
Display
level
Setting range Initialvalue
RTS
Retransmission
output type of RET
EASY
OFF: Disable
PV1:PV
SP1: SP
OUT1:OUT
(Valveopening:0to
100%inPositionproportional
control)
LPS:15VDClooppowersupply
PV2:Loop-2PV
SP2: Loop-2 SP
OUT2: Loop-2 OUT
TSP1: Target SP
HOUT1: Heating-side OUT
COUT1: Cooling-side OUT
MV1:Positionproportionaloutput
internal computed value)
TSP2: Loop-2 target SP
HOUT2: Loop-2 heating-side OUT
COUT2: Loop-2 cooling-side OUT
MV2:Loop-2positionproportional
output (internal computed
value)
PV:PVterminalsanaloginput
RSP: RSP terminals analog input
AIN2: AIN2 terminals analog input
AIN4: AIN4 terminals analog input
Loop-2 setting values are
unavailable in Single-loop
control.
PV1
RTH
Maximum value
of retransmission
output scale of RET
STD
WhenRTS
=PV1,SP1,PV2,SP2,
TSP1,TSP2,PV,RSP,AIN2,or
AIN4,
RTL + 1 digit to 30000
-19999 to RTH - 1 digit
Decimal point position:
WhenRTS=PV1,SP1,orTSP1,
decimal point position is same
asthatofPVinput.
WhenRTS=PV2,SP2,orTSP2,
decimal point position is same
as that of RSP input.
WhenRTS=PV,decimalpoint
positionissameasthatofPV
input scale.
WhenRTS=RSP,decimalpoint
position is same as that of RSP
input scale.
WhenRTS=AIN2,decimalpoint
position is same as that of AIN2
scale.
WhenRTS=AIN4,decimalpoint
position is same as that of AIN4
scale.
100%ofPV
input range
RTL
Minimum value
of retransmission
output scale of RET
STD
0%of
PV
input range
18.2ListofParameters