Parameters 187
01.20 RUN TIME
COUNTER
Counts the running time of the motor.
The counter runs only when drive modulates. The
value is protected against power failure.
The counter can be reset using the DriveStudio tool.
The counter can only be set to zero.
- / INT32
0.0...
35791394.1 h
Motor run time in hours.
- / 100 = 1 h
01.21 FAN ON-TIME
Counts the running time of the drive cooling fan.
The counter can be reset by entering 0. The value is
protected against power failure.
The counter can only be set to zero.
- / INT32
0.0...
35791394.1 h
Cooling fan run time in hours.
- / 100 = 1 h
01.22 TEMP INT BOARD
Shows the measured temperature of the interface
board.
- / Real24
-40.0...160 °C Interface board temperature in Celsius 10 = 1 °C / -
01.23 SPEED FILT
Shows the filtered motor speed.
Filtering time = 250 ms.
- / Real
-30000.0...
30000.0 rpm
Filtered motor speed in rpm.
- / 10 = 1 rpm
01.24 TORQUE FILT
Shows the filtered motor torque.
Filtering time = 100 ms.
- / Real
-1600.0...
1600.0%
Filtered motor torque in percent.
10 = 1% / -
01.25 FAN START
COUNT
Shows the number of times drive fan was started. - / Real
0...2147483647 Drive fan start count. 1 = 1
01.26 TORQ MAX LIM
Shows the active torque limit. - / Real
0...1600% Active torque limit in percent.
1 = 1% / -