224 Parameters
13.08 AI2 MIN
Defines the minimum value for analogue input AI2.
The type is selected with jumper J2 on the JCU
Control Unit.
-10.000 V/
Real
-11.000…
11.000 V /
-22.000…
22.000 mA
Minimum AI2 input value. 1000 = 1 V
or mA / -
13.09 AI2 MAX SCALE
Defines the real value that corresponds to the
maximum analogue input value defined by
parameter 13.07 AI2 MAX.
100.000/
Real
-32768.000
…32768.000
Real value corresponding to the value of parameter
13.07.
- / 1000 = 1
13.10 AI2 MIN SCALE
Defines the real value that corresponds to the
minimum analogue input value defined by parameter
13.08 AI2 MIN. See parameter 13.09 AI2 MAX
SCALE.
-100.000/
Real
-32768.000
…32768.000
Real value corresponding to the value of parameter
13.08.
- / 1000 = 1
13.11 AITUNE
Triggers the AI tuning function.
Connect the signal to the input and select the
appropriate tuning function.
No action/
enum
No action AI tune is not activated. 0
AI1 min tune Current analogue input AI1 signal value is set as
minimum value for AI1, parameter 13.03 AI1 MIN.
The value reverts back to No action automatically.
1
No. Bit/Name/Value/
Range
Description Def/Type
FbEq
(16b/32b)
AI (scaled)
AI (mA / V)
13.07
13.08
13.10
13.09