232 Parameters
16.09 USET IO SEL LO
Together with parameter 16.10 USET IO SEL HI,
selects the user parameter set when parameter
16.07 USER SET SEL is set to IO mode. The status
of the source defined by this parameter and
parameter 16.10 selects the user parameter set as
follows:
C.False /
Bit pointer
Bit pointer: CONST or POINTER (See Terms and
abbreviations on page 183.)
16.10 USET IO SEL HI
See parameter 16.09 USET IO SEL LO. C.False /
Bit pointer
Bit pointer: CONST or POINTER (See Terms and
abbreviations on page 183.)
16.11 TIME SOURCE
PRIO
Selects which real-time clock source is adopted by
the drive as the master real-time clock. Some
selections specify multiple sources that are in the
order of priority.
FB_MMI /
enum
FB_MMI Fieldbus (highest priority); man-machine interface
(control panel or PC).
0
FB only Fieldbus only. 4
MMI_FB Man-machine interface (control panel or PC) (highest
priority); fieldbus; drive-to-drive link.
6
MMI only Man-machine interface (control panel or PC) only. 7
Internal No external sources are used as master real-time
clock.
8
No. Bit/Name/Value/
Range
Description Def/Type
FbEq
(16b/32b)
Status of
source defined
by par. 16.09
Status of
source defined
by par. 16.10
User
parameter set
selected
FALSE FALSE Set 1
TRUE FALSE Set 2
FALSE TRUE Set 3
TRUE TRUE Set 4