Parameters 257
58.03 NODE ADDRESS
Defines the node address. 1 / Real
0…247
Node address.
1 = 1
58.04 BAUD RATE
Selects the baud rate of the RS-485 link. 9600 / enum
4800
4.8 kbit/s.
0
9600 9.6 kbit/s.
1
19200 19.2 kbit/s.
2
38400 38.4 kbit/s.
3
57600 57.6 kbit/s.
4
76800 76.8 kbit/s.
5
115200 115.2 kbit/s.
6
58.05 PARITY
Selects the number of the data bits, the use and type
of the parity bit, and the number of the stop bits.
8 NONE 1 /
enum
8 NONE 1 Eight data bits, no parity bit, one stop bit.
0
8 NONE 2 Eight data bits, no parity bit, two stop bits.
1
8 EVEN 1 Eight data bits, even parity bit, one stop bit.
2
8 ODD 1 Eight data bits, odd parity bit, one stop bit.
3
58.06 CONTROL
PROFILE
Selects the communication profile used by the
Modbus protocol.
ABB
ENHANCED
/ enum
ABB CLASSIC ABB Drives profile, classic version.
0
ABB ENHANCED ABB Drives profile, enhanced version.
1
DCU 16-BIT DCU 16-bit profile.
2
DCU 32-BIT DCU 32-bit profile.
3
58.07 COMM LOSS T
OUT
Defines the timeout limit for EFB communication loss
monitoring.
If a communication break exceeds the timeout limit,
the function proceeds with the action defined with
parameter 58.09 COMM LOSS ACTION. See also
parameter 58.08 COMM LOSS MODE.
600 ms /
Real
0…60000 ms Timeout calculation factor. The actual timeout value
is calculated as follows:
Comm loss timeout × 100 ms
Example: If you set this value to 22, the actual
timeout value will be: 22 × 100 ms = 2 200 ms.
100 = 1 ms
58.08 COMM LOSS
MODE
Enables/disables EFB communication loss
monitoring and defines which of the Modbus register
accesses resets the timeout counter. See parameter
58.07 COMM LOSS T OUT.
NONE /
enum
NONE EFB communication loss monitoring is disabled.
0
No. Bit/Name/Value/
Range
Description Def/Type
FbEq
(16b/32b)