256 Parameters
52
52 FBA DATA IN
Selection of the data to be sent by the drive to the
fieldbus controller. These parameters need to be set
only if a fieldbus adapter module is installed.
52.01 FBA DATA IN1
Selects data to be transferred from the drive to the
fieldbus controller.
0 / UINT32
0NOT USED. 0
4 Status Word (16 bits). 4
5 Actual value 1 (16 bits). 5
6 Actual value 2 (16 bits). 6
14 Status Word (32 bits). 14
15 Actual value 1 (32 bits). 15
16 Actual value 2 (32 bits). 16
101…9999 Parameter index. 101…9999
52.02 FBA DATA IN2
... ...
52.12 FBA DATA IN12
See 52.01 FBA DATA IN1. - / UINT32
53
53 FBA DATA OUT
Selection of the data to be sent by the fieldbus
controller to the drive. These parameters need to be
set only if a fieldbus adapter module is installed.
53.01 FBA DATA OUT1
Selects data to be transferred from the fieldbus
controller to the drive.
0 / UINT32
0NOT USED. 0
1 Control Word (16 bits). 1
2 Reference REF1 (16 bits). 2
3 Reference REF2 (16 bits). 3
11 Control Word (32 bits). 11
12 Reference REF1 (32 bits). 12
13 Reference REF2 (32 bits). 13
1001…9999 Parameter index. 1001… 9999
... ...
... ...
53.12 FBA DATAOUT12
See 53.01 DATA OUT1. - / UINT32
58
58 EMBEDDED
MODBUS
Configuration parameters for the embedded fieldbus
(EFB) interface.
58.01 PROTOCOL ENA
SEL
Enables/disables the embedded fieldbus
communication protocol.
DISABLED /
enum
DISABLED Disabled.
0
MODBUS RTU Modbus RTU protocol enabled.
1
No. Bit/Name/Value/
Range
Description Def/Type
FbEq
(16b/32b)