Fault tracing 301
0012
BR OVERHEAT Brake resistor temperature
has exceeded the fault limit
defined with parameter
48.05 BR TEMP
FAULTLIM.
Stop the drive. Let the resistor cool
down.
Check resistor overload protection
function settings, parameters
48.01…48.04.
Check the fault limit setting,
parameter 48.05.
Check that the braking cycle meets
allowed limits.
0013
CURR MEAS GAIN Difference between output
phase U2 and W2 current
measurement gain is too
great.
Contact your local ABB
representative.
0014
CABLE CROSS
CON
Programmable
fault: 48.05 CROSS
CONNECTION
Incorrect input power and
motor cable connection (ie,
the input power cable is
connected to the drive
motor connection).
Check input power connections.
0015
SUPPLY PHASE
Programmable
fault: 46.04 SUPPL
PHS LOSS
Intermediate circuit DC
voltage is oscillating due to
missing input power line
phase or blown fuse.
Check input power line fuses.
Check for input power supply
imbalance.
0016
MOTOR PHASE
Programmable
fault: 46.02 MOT
PHASE LOSS
Motor circuit fault due to
missing motor connection
(all three phases are not
connected).
Connect the motor cable.
0017
ID-RUN FAULT Motor ID Run is not
completed successfully.
Check the fault logger for a fault
code extension. See the
appropriate actions for each
extension below.
Fault code
extension: 1
The ID run cannot be
completed because the
maximum current setting
and/or the internal current
limit of the drive is too low.
Check the settings of parameters
99.03 MOT NOM CURRENT and
20.02 MAXIMUM CURRENT. Make
sure that 20.02 MAXIMUM
CURRENT > 99.03 MOT NOM
CURRENT.
Check that the drive is
dimensioned correctly according to
the motor.
Code Fault Cause What to do