Installer manual AlphaVision ML Rev. 3.60 01-01-2015 10
The label of the I/O module is placed in the metal housing on the inside back wall of the back casing.
Labels should not be removed!
If the installation does not meet grade 1, 2 or 3 labels MUST be removed or otherwise made clear
that the installation of non-compliant!
The separate serial number label must never be removed.
Application: Residential and industrial market.
Zones: 8 wired zones
Outputs AlphaVision I/O module:
Speaker (LS) output 8 ohm 15W
2 floating relay contacts (maximum current through the contact is max 300mA @ 12VDC)
6 Open Collector (OC) outputs, 200mA maximum load. On these outputs the connected cable may
not exceed 3m. The outputs 3 and 4 are protected with a poly fuse of 200mA, the outputs 5 to 8
contain a serie resistor of 27E / 0.1 W.
4 connections (outgoing) +12 V supply voltage, divided into 2 pieces 2-pole connector (containing a
750mA fuse)
The +12 V terminal blocks provide a continuous supply voltage between 9.0 and 14.5 VDC. The total (all
+12 V connectors) power consumption from the I/O module for a grade 3 installation may not exceed
450mA. If more power is required, this must be solved through an external power supply, for example using
an additional I/O module. The maximum ripple on the output voltage is 250mV.
Backup battery: in the metal casing there is room for a 7Ah or 17Ah lead acid battery.
Service: The Alpha Vision I/O module does not have any “serviceable” parts. When defects (in consultation)
are detected the pcb board of the I/O module must be replaced. The battery must be replaced after the
expected life (3-5 years) during the annual maintenance check.
The value of the fuse in the 230V terminal block is S1.6A L250V (1.6 A slow 5x20mm). The value of the fuse
in the red battery wire is F5A 250V (5A fast 6x32mm).
The AlphaVision ML, I/O module and associated boards apply with the following European standards:
EMC omission EN301489-3 2002
EMC immunity EN50130-4 2003
Radio EN300220-3
Telephone (PSTN) TBR21 1998
Safety class European norm EN60950
Security class
*)
European norm EN50131-1 according to “grade 2 – low
to medium risk” and “environmental class II – Indoor
general”
*)
The requirements for a grade 2 system, such as those expressly mentioned in this manual, should be
strictly followed